
Chapter 6 Device Control and Upgrading
Resetting Accumulators and Log Files
EM720 Power Quality and Revenue Meter
131
Access to the RESET menu entries is allowed depending on
your security level as shown in the following table. Clearing
files is not allowed from the front display.
Reset Entry
Menu Function
Security
Level
Diagnostics
Reset of device diagnostics
Low
Bill/TOU MD
Reset of billing maximum demands and triggering an
end of billing period
Low
Power MD
Volt/Amp MD
Volt MD
Ampere MD
Harmonic MD
All MD
Reset of engineering maximum demands
Low
Dev.Oper.Time Reset of the meter operation time counters
Medium
Lith.Bat.Time
Reset of the lithium battery operation time counters
Medium
Aux.Bat.Time
Reset of the rechargeable auxiliary battery operation
time counters
Medium
Power Failures
Reset of the meter failure counters
Medium
To reset a desired entry:
1. Use the SCROLL button to scroll through the menu
entries until a required reset entry appears in the
window.
2. Press briefly SELECT/ENTER button to highlight the
“Do” entry.
3. Press and hold the SELECT/ENTER button for more
than 5 seconds until the “Do” entry is replaced with
“Done” indicating that the operation is complete.
4. Release the button.
If your security level does not allow access to a menu entry,
you will not be able to highlight the lower action window.
NOTE
You may not be allowed to reset the billing maximum
demands in the event this action is not enabled for the front
display in the Device Options setup, or it has been just
performed once at the same day – the meter does not allow
repeated triggering an end of billing period within one
calendar day.
Using PAS
Select Reset from the Monitor menu.
Refer to the table above for required permissions. To clear
log files, you should have the administration rights.
NOTE
The “Clear All Log Files” entry does not affect billing data and
energy load profile files.
EXTENDED PRESS
ENTER
SHORT PRESS
SELECT
SCROLL