Menu-driven setups
Digital I/O
•
Four embedded digital inputs with 1 ms scan time
•
Replaceable 2DI/2DO expansion I/O modules with 1/2
cycle scan/update time
Memory
•
8 or 16 Mbyte flash memory for long-term billing,
event, waveform and data recording
Communications
•
Front Infrared IEC 62056-21 serial communication port
(IEC 62056-21, Modbus RTU/ASCII and DNP3
protocols)
•
Plug-in serial RS232/RS485 communication port
(Modbus RTU/ASCII and DNP3 protocols)
•
Plug-in full speed USB 1.1 port (Modbus RTU protocol)
•
Plug-in Ethernet port (Modbus/TCP and DNP3/TCP
protocols, IEC 61850 – future releases), up to 5
simultaneous connections
•
Plug-in wireless GSM/GPRS modem (Modbus/TCP and
DNP3/TCP protocols)
Expansion I/O and Communication slots
•
3 expansion slots for plug-in I/O and communication
modules
Backup Power Supplies
•
Rechargeable auxiliary battery (more than 3 hours
operation time with a NiMH battery, up to 7 hours
operation with a Li-Ion battery)
•
Auxiliary 24VDC backup power supply module
•
Auxiliary 85-265VAC/90-290VDC backup power supply
module
Upgradeable Firmware
•
New features can be easily added to your meter by
simply replacing firmware through any communication
port.
Software Support
•
PAS – free meter configuration and data acquisition
tool
•
eXpertPower
TM