Appendix D EN50160 Statistics Log Files
EM720 Power Quality and Revenue Meter
201
Field No.
Designation Description
6
N21 110%/60s
Number of polyphase incidents u>110%/t<60s
7
N22 120%/60s
Number of polyphase incidents u>120%/t<60s
8
N23 140%/60s
Number of polyphase incidents u>140%/t<60s
9
N24 160%/60s
Number of polyphase incidents u>160%/t<60s
10
N25 200%/60s
Number of polyphase incidents u>200%/t<60s
11
N31 110%/>60s Number of polyphase incidents u>110%/t>60s
12
N32 120%/>60s Number of polyphase incidents u>120%/t>60s
13
N33 140%/>60s Number of polyphase incidents u>140%/t>60s
14
N34 160%/>60s Number of polyphase incidents u>160%/t>60s
15
N35 200%/>60s Number of polyphase incidents u>200%/t>60s
16
V1 N1
Total number of incidents on phase V1
17
V1 Max
Maximum voltage magnitude on phase V1
18
V2 N1
Total number of incidents on phase V2
19
V2 Max
Maximum voltage magnitude on phase V2
20
V3 N1
Total number of incidents on phase V3
21
V3 Max
Maximum voltage magnitude on phase V3
Transient Overvoltages (peak voltage)
1
N1 120%
Number of polyphase incidents u>120%
2
N2 150%
Number of polyphase incidents u>150%
3
N3 200%
Number of polyphase incidents u>200%
4
N4 250%
Number of polyphase incidents u>250%
5
N5 300%
Number of polyphase incidents u>300%
6
V1 N1 120%
Number of incidents u>120% on phase V1
7
V1 N2 150%
Number of incidents u>150% on phase V1
8
V1 N3 200%
Number of incidents u>200% on phase V1
9
V1 N4 250%
Number of incidents u>250% on phase V1
10
V1 N5 300%
Number of incidents u>300% on phase V1
11
V2 N1 110%
Number of incidents u>120% on phase V2
12
V2 N2 150%
Number of incidents u>150% on phase V2
13
V2 N3 200%
Number of incidents u>200% on phase V2
14
V2 N4 250%
Number of incidents u>250% on phase V2
15
V2 N5 300%
Number of incidents u>300% on phase V2
16
V3 N1 110%
Number of incidents u>120% on phase V3
17
V3 N2 150%
Number of incidents u>150% on phase V3
18
V3 N3 200%
Number of incidents u>200% on phase V3
19
V3 N4 250%
Number of incidents u>250% on phase V3
20
V3 N5 300%
Number of incidents u>300% on phase V3
21
V1 Peak Max
Maximum peak voltage on phase V1
22
V2 Peak Max
Maximum peak voltage on phase V2
23
V3 Peak Max
Maximum peak voltage on phase V3
Transient Overvoltages (impulsive voltage)
1
N1 20%
Number of polyphase incidents u>20%
2
N2 50%
Number of polyphase incidents u>50%
3
N3 100%
Number of polyphase incidents u>100%
4
N4 150%
Number of polyphase incidents u>150%
5
N5 200%
Number of polyphase incidents u>200%
6
V1 N1 20%
Number of incidents u>20% on phase V1
7
V1 N2 50%
Number of incidents u>50% on phase V1
8
V1 N3 100%
Number of incidents u>100% on phase V1
9
V1 N4 150%
Number of incidents u>150% on phase V1
10
V1 N5 200%
Number of incidents u>200% on phase V1