17 

 

Smoking 

 

 

chimney draught not  
sufficient 

check chimney’s permeability 
and its parameters  (see  tab. 
height and section to boiler’s 
power p. 11-12 ), check if 
chimney end is not lower than 
roof  ridge 

gases channels dirty 

clean up boiler through washout 
holes 

sealing rope indoor and 
washout openings worn 

replace a rope (to be replaced  
regularly) 

improper assembly of 
boiler and  
chimney connection 

check accurateness 

 

 

very low atmospheric 
pressure   

 

 

improper position of 
smoke throttle to current 
chimney draught 

 

adjust sprocket position if it is  
closed to much 

 

 

Sudden temperature  
and pressure rise 

 

installation valves closed 

 

open the valves 

 

pressure vessel frozen 

 

heat the pressure vessel 

 

Water licking out of  
boiler 

so called. "boiler’s 
sweating", this is natural 
process caused by 
temperature difference in 
boiler    

during boiler’s start-up and after  
each standby "heat the boiler" 
e.g. burn it up to 70°C  and keep 
that temperature for several 
hours 

"Hitting, shooting" 

 

in boiler 

 

air in the heating 
installation and boiler 
due to improperly 
performed filling in 
process 

"heat the boiler" e.g. burn it up to 
70°C  and keep that temperature  
for a longer time, till the whole 
air  
is removed from boiler remove  
the  air  from  installation  
by  opening  the  valves  on  
radiators. 

 
 
 
 
 
 
In    order    to    ensure    the    failure-free    and    safe    operation    (to    maximum    extent)    the  
controller    of    boiler    is  provided  with    many    protection    functions.  If  faulty    status    is  
discovered,  the    alarm    is  launched    (acoustic  signal),  and  a  message  is  shown  on  display 
(depending on controller version). 
 
TERMAL PROTECTION
 
The  controller  is  equipped  with  safety  temperature  limiter,  preserving  the boiler  against 
overheating (boiling water in installation),  if the controller is  damaged. Temperature limiter 
makes up  mechanical protection measure, which bimetallic sensor (placed at the boiler water

 

10.

  

PROTECTION MEANS

 

Summary of Contents for NWT

Page 1: ...L A R S K I 28 100 Busko Zdr j Owczary ul Przemys owa 3 Phone 48 41 378 46 19 Fax 48 41 370 83 10 TECHNICAL START UP DOCUMENTATION of water boiler s for heating installations SAS NWT type adopted for...

Page 2: ...r to a heating installation 8 6 5 Connecting boilers to electrical installation 9 7 Operation and installation guidelines 9 7 1 Filing with water 9 7 2 Boiler s firing up 10 Table technical exploitati...

Page 3: ...3...

Page 4: ...4...

Page 5: ...ler is 0 30 0 55 mbar depending on boiler s power These boilers may also work in hot water installations utilizing a heat exchanger Boiler s selection for building heating should be based on heat bala...

Page 6: ...neral wool which fill the space between the heat exchanger and boilers casing pos 1 Coal heating boilers of SAS NWT type are equipped with a controller and blow in fan Boilers work based on the proces...

Page 7: ...cal Start Up Documentation 6 1 REQUIREMENTS FOR BOILER ROOM The boiler room where the heating boiler for central heating installation shall be installed must conform the requirements of detailed regul...

Page 8: ...on detailed regulations being in force in the country of destination Assuming that it is not possible to achieve such parameters for chimney and chimney draught problems are experienced resulting in i...

Page 9: ...r temperature below 55 C then the boiler should be connected to the heating installation equipped with three or four pass valve protecting it against low temperature corrosion 6 5 CONNECTING BOILER TO...

Page 10: ...pieces of paper and wood Then thin layer of coal is applied Once a coal is glowing the ash box and furnace door must be closed Open fuel charge door and fill the combustion chamber with fuel reaching...

Page 11: ...g pressure bar 1 5 11 Maximal allowable working temp C 85 12 Recommended heating water working temp C 60 80 13 Minimal return water temp C 55 14 Power supply V Hz 15 Power consumption 16 Dimensions A...

Page 12: ...735 785 835 885 885 935 985 985 1035 H 1500 1560 1560 1560 1610 1635 1685 1735 1735 1780 1830 1830 1870 H1 1470 1530 1530 1530 1580 1605 C 1655 C 1705 C 1705 C 1750 C 1800 C 1800 C 1840 C H2 350 300 3...

Page 13: ...r jacket 8 glow prevention grid 13 smoke conduit cleaning hole 18 blowdown connection 23 temperature regulator controller 4 furnace chamber 9 water grates 14 smoke throttle 19 hot water connector pipe...

Page 14: ...tion connector pipe 3 water jacket 8 water grate 13 temperature sensor well 18 smoke conduit cleaning hole 23 blowdown connection 4 return water connector pipe 9 furnace chamber 14 hot water connector...

Page 15: ...troller keeps it constant If boiler s temperature is lower than set rotation speed of fan is increased if it is higher scavenges of the boiler are only performed 7 4 CLEANING THE BOILER In order to us...

Page 16: ...fire up a boiler by use of petrol kerosene solvents explosion may occur causing he operator to be burned in case of installation malfunction and lacking water in a boiler do not fill it in if boiler...

Page 17: ...r s start up and after each standby heat the boiler e g burn it up to 70 C and keep that temperature for several hours Hitting shooting in boiler air in the heating installation and boiler due to impr...

Page 18: ...ng a boiler to a heating installation make check if all boiler s components are in good working condition and that the boiler is fully equipped NOTE Boilers need to be transported in the vertical posi...

Page 19: ...lized by manufacturer is only possible based o expert opinion that repair is not workable 10 If the advertiser does not allow double warranty repairs despite the willingness of the guarantor to comply...

Page 20: ...tation shall be addressed ZAK AD METALOWO KOTLARSKI Owczary ul Przemys owa 3 28 100 Busko Zdr j Tel 4841 378 46 19 Fax 4841 370 83 10 http www sas busko pl e mail biuro sas busko pl serwis sas busko p...

Page 21: ...21 SERVICE REPAIRS...

Page 22: ...mperature boiler of SAS NWT type installed and operated in pursuance of Technical Start Up Documentation Boiler no Heating capacity Heated surface Year of manufacture Manufacturer signature and stamp...

Reviews: