17
Smoking
chimney draught not
sufficient
check chimney’s permeability
and its parameters (see tab.
height and section to boiler’s
power p. 11-12 ), check if
chimney end is not lower than
roof ridge
gases channels dirty
clean up boiler through washout
holes
sealing rope indoor and
washout openings worn
replace a rope (to be replaced
regularly)
improper assembly of
boiler and
chimney connection
check accurateness
very low atmospheric
pressure
improper position of
smoke throttle to current
chimney draught
adjust sprocket position if it is
closed to much
Sudden temperature
and pressure rise
installation valves closed
open the valves
pressure vessel frozen
heat the pressure vessel
Water licking out of
boiler
so called. "boiler’s
sweating", this is natural
process caused by
temperature difference in
boiler
during boiler’s start-up and after
each standby "heat the boiler"
e.g. burn it up to 70°C and keep
that temperature for several
hours
"Hitting, shooting"
in boiler
air in the heating
installation and boiler
due to improperly
performed filling in
process
"heat the boiler" e.g. burn it up to
70°C and keep that temperature
for a longer time, till the whole
air
is removed from boiler remove
the air from installation
by opening the valves on
radiators.
In order to ensure the failure-free and safe operation (to maximum extent) the
controller of boiler is provided with many protection functions. If faulty status is
discovered, the alarm is launched (acoustic signal), and a message is shown on display
(depending on controller version).
TERMAL PROTECTION
The controller is equipped with safety temperature limiter, preserving the boiler against
overheating (boiling water in installation), if the controller is damaged. Temperature limiter
makes up mechanical protection measure, which bimetallic sensor (placed at the boiler water
10.
PROTECTION MEANS