(2) Place a plastic sheet under the drain pan so that the residual water in the drain will not make the floor wet.
(Fig.35)
(3) Disconnect the flare nut for wide tube by 2 wrenches. (Fig.36
)
In case that a drain hose is buried inside a wall, remove it after the drain hose in the wall
is pulled out.
(4)
Disconnect the flare nut for narrow tube by 2 wrenches. (Fig.37)
When disconnecting tubes, cover every nozzle with caps so as not to let dust and moisture in.
Fig. 34
Fig. 35
Fig. 36
Fig. 37
NOTE
NOTE
9-1-8. Disconnecting the refrigerant piping
(1)
Lift the indoor unit by a wooden base. (Fig.34)
If gas leaks, repair the spot of leaking, then collect all refrigerant from
the unit. After conducting vacuum drying, recharge proper amount of
refrigerant.
Caution
Do not mix any gas (including air) other than the specified refrigerant
(R-410A) into refrigerant cycle.
If air or other contaminants mix with the gas, pressure will become
extremely high in the refrigerating cycle, which may cause a unit breakdown
or personal injuries.
Caution
Wooden base
Drain hose
Extension drain hose
Connecting wires
51