3
2-2. Unit Specifications
The following are the specifications with the electric current suppressor set to “FREE.” (Please refer to 8-4 for
details)
Indoor unit
SAP-KMV91G
Outdoor unit
SAP-CMV2441G
NOTE
No. of Indoor Units
1-unit type
Power Source
220 – 230V ~ 50Hz
Cooling
Capacity
kW
2.6 (0.8 – 2.9)
BTU/h
8,900 (2,700 – 9,900)
Air circulation (High)
m
3
/ h
430
Moisture removal (High)
Liters/ h
1.3
Voltage rating
V
230
Available voltage range
V
198 – 253
Running amperes
A
5.9 (2.2 – 7.1)
Power input
W
1,070 (380 – 1,360)
Power factor
%
79
C.O.P.
W/W
2.4
Compressor locked rotor amperes
A
23
Controls / Temperature control
Microprocessor / I.C. thermostat
Control unit
Wireless remote control unit
Timer
ON/OFF 24-hours & Daily program, 1-hour OFF
Fan speeds
Indoor / Outdoor
3 and Auto / Auto (Variable)
Airflow direction (Indoor)
Horizontal
Manual
Vertical
Auto
Air filter
Washable, Anti-mold
Compressor
Rotary (Hermetic)
Refrigerant / Amount charged at shipment
g
R22 / 2,500
Refrigerant control
Electrical expansion valve
Operation sound
Indoor – Hi / Me / Lo
dB-A
39 / 35 / 31
Outdoor – Hi
dB-A
47
Refrigerant tubing connections
Flare type
Max. allowable tubing length at shipment
m
20
Refrigerant tube
Narrow tube
mm (in.)
6.35 (1/4)
diameter
Wide tube
mm (in.)
12.7 (1/2)
Refrigerant tube kit / Accessories
Optional / Hanging wall bracket
Indoor unit
Outdoor unit
Unit dimensions
Height
mm
250
625
Width
mm
790
880
Depth
mm
174
295
Package dimensions
Height
mm
242
699
Width
mm
850
1,126
Depth
mm
312
401
Weight
Net
kg
7.0
63.0
Shipping
kg
10.0
68.0
Shipping volume
m
3
0.063
0.316
Performance
Electrical Rating
Features
Dimensions & Weight
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks: Rating conditions are:
Cooling: Indoor air temperature
27°C D.B. / 19°C W.B.
Outdoor air temperature 35°C D.B. / 24°C W.B.