When using the supplied “SANUPS SOFTWARE STANDALONE”, note the following instructions for the
items on the main screen.
See §6.1 “Main Screen” in the User Guide of SANUPS SOFTWARE STANDALONE for details.
Main screen of SANUPS SOFTWARE STANDALONE
“
“
C
C
h
h
a
a
r
r
g
g
e
e
”
”
o
o
f
f
B
B
a
a
t
t
t
t
e
e
r
r
y
y
(1) If UPS is not charged for 24 hours (A11H***011) or 36 hours (A11H***111) or more when the UPS first
started, “Charge” is not displayed properly. See §8.2 “UPS Charge” to charge the UPS.
(2) If the UPS is stopped and then restarted, even when the UPS is charged enough, “Charge” might be
displayed as “80%” or “90%”. This occurs due to the operating conditions such as ambient temperature.
In this case, “Charge” will be displayed properly, if UPS is operated normally for 1 or 2 hours.
(3) Connect the battery connector correctly. If the UPS is operated without the batteries, “Charge” might
show a value lower than the actual charge rate. Moreover, even if the battery connector is reconnected
and operates the UPS, the proper charge rate is not displayed immediately.
In this case, “Charge” will be displayed properly, if UPS is operated normally for 24 or 36 hours or
more.
(4) Display of “Charge” is only an approximation. An actual charge rate of the battery might differ slightly.
“
“
B
B
a
a
c
c
k
k
u
u
p
p
t
t
i
i
m
m
e
e
”
”
o
o
f
f
B
B
a
a
t
t
t
t
e
e
r
r
y
y
(1) In “Setting the shutdown trigger conditions” of SANUPS SOFTWARE STANDALONE, if “When the
backup-time is under the specified value.” is selected as the shutdown trigger conditions, set the time
more than 40% of the backup time displayed on the main screen.
Refer to §6.4 “Setting the Shutdown Conditions” in the User Guide of SANUPS SOFTWARE
STANDALONE for details.
(2) If the “Load” displayed on the main screen is less than 30%, the backup time sometimes shows
improper value.
(3) “Backup time” displayed is only an approximation. An actual backup time might differ slightly.