User Settings Guide
No.
Ref. page
Item
Menu
Menu LED
Setting
Setting
LED
Default
Setting
Current
Setting
Remarks
-
●○○○
-
○●○○
-
●●○○
Do not use these settings.
1 4 3.1
Output voltage
○
● ○ ○ ○
120 V
○○●○
*
120 V
1%
●○○○
±
1%
3%
○●○○
±
3%
2
5
3.2
Frequency sync
range (RESTART)
○
○ ● ○ ○
5%
●●○○
*
±
5%
Output frequency variation range (%)
50Hz
●○○○
50Hz
3 6 3.3
Output frequency
(RESTART)
○
● ● ○ ○
60Hz
○●○○
*
60Hz
Standalone
●○○○
Set when using UPS remote ON/OFF or Standard OS UPS
Services
Workstation
○●○○
*
Set when using a power management software, LAN card or
UPS remote ON and One-touch system shutdown.
Serial Login
●●○○
Shutdown by serial login.
4
7
3.4
PC interface
○
○ ○ ● ○
-
○○●○
Do not use this setting.
9600
●○○○
*
9600 bps.
4800
○●○○
4800 bps.
5 8 3.5
Serial baud rate
○
● ○ ● ○
2400
●●○○
2400 bps.
Set the serial baud rate when a
workstation, PC, or optional LAN
card is connected.
Auto
●○○○
*
Auto restart
OFF
○●○○
The UPS stays off.
30%
●●○○
Auto restart when battery
charge reaches 30%.
50%
○○●○
Auto restart when battery
charge reaches 50%.
6
9
3.6
UPS operation upon
power recovery
○
○ ● ● ○
80%
●○●○
Auto restart when battery
charge reaches 80%.
Specify when to restart the UPS
after a power outage and
shutdown of the UPS due to final
discharge of the batteries.
All patterns
●○○○
*
All sounds
Pattern 1
○●○○
Emit sounds on serious failure and battery trouble.
Pattern 2
●●○○
Emit alarm and key click sounds.
7 10 3.7
Buzzer sound
○
● ● ● ○
OFF
○○●○
Emit key click sounds only.
1 second
●○○○
*
Turn the UPS off when
pressed for 1 second.
3 seconds
○●○○
Turn the UPS off when
pressed for 3 second.
8
11
3.8
Shutdown operation
○
○ ○ ○ ●
Special
operation
●●○○
Turn the UPS off on
special operation.
Set the operation for switch to stop
the UPS power supply.
Auto return
●○○○
Auto recovery when a
certain period of time has
elapsed.
9 12 3.9
Overload recovery
operation
○
● ○ ○ ●
Bypass
○●○○
*
Fixed as bypass power
supply on overload.
Set the UPS operation after
switching to the bypass power
supply because of overload.
OFF
●○○○
*
The UPS stays off.
10 13 3.10
UPS operation at
OFF
(RESTART)
○
○ ● ○ ●
Bypass
○●○○
Bypass power supply
Specify the UPS power supply
conditions when
is off.
Battery voltage
●○○○
*
When low battery voltage
level is detected.
2 minutes
○●○○
When remaining battery
duration is 2 minutes.
11 14 3.11
Low battery voltage
warning timing
○
● ● ○ ●
3 minutes
●●○○
When remaining battery
duration is 3 minutes.
Set the timing of emitting the low
battery voltage warning alarm
(beep, Red BATT. LOW lit).
12 min. 10 min.
●○○○
20 min. 18 min.
○●○○
See
remarks
Set the UPS backup time on power outage.
-
○●●○
-
●●●○
-
○○○●
-
○●●○
-
●●●○
-
○○○●
-
●○○●
-
○●○●
12 15 3.12
Battery backup time
○
○ ○ ● ●
-
●●○●
Do not use these settings.
Default setting varies depending
on UPS Model.
Default setting of each Model is as
follows.
A11H202U011TW : 12 minutes
A11H202U111TW : 20 minutes
A11H302U011TW : 10 minutes
A11H302U111TW : 18 minutes
5 years
●○○○
*
5 years lifetime type
10 years
○●○○
10 years lifetime type
13 16 3.13
Battery type
○
● ○ ● ●
3 years
●●○○
3 years lifetime type
Set the battery type. Set this when
you replace the battery or connect an
external battery.
180 days
●○○○
*
Test batteries every 180 days.
90 days
○●○○
Test batteries every 90 days.
30 days
●●○○
Test batteries every 30 days.
14 17 3.14
Battery test schedule
○
○ ● ● ●
None
○○●○
No battery check.
Set the interval (number of days)
for the automatic battery check.
The check is carried out
automatically when the specified
number of days has elapsed.
Do not reset
●○○○
*
Do not reset.
15 18 3.15
Reset battery
information
○
● ● ● ●
Reset
○●○○
Reset the battery information when you replace the battery.
●