Using Standard OS UPS Services
48
§
§
1
1
7
7
.
.
2
2
Windows 2000/XP/Server 2003
To make UPS settings, log in as a user with Administrator privileges.
①
Select the “Power Option Properties” icon in the Control Panel, and then click the “Select...” button in the
UPS tab.
②
Select “Generic” in the “Select manufacturer” list, select “Custom” in the “Select model” list, and then click
“Next”.
③
Make the settings shown in the following figure, and then click “Finish”.
(Select the “Positive” option before clearing the check from the UPS Shutdown check box.)
No.
Item
Description
A Power Fail/On Battery
Specifies that a warning message should be displayed according to the settings in
the “UPS Service” section.
B Low Battery
Specifies that the OS shutdown should begin on reception of a UPS low battery
signal.
C UPS Shutdown
Clear this check box.
Even if you enable “UPS Shutdown”, the UPS
will not shut down automatically after
Windows 2000/XP/Server 2003 shutdown.
If you need automatic UPS shutdown, use the
optional power management software.
Note
Click Select...
A
B
C