Chapter 6. Profile
34
▶
Control word (Object: 0x6040)
It is the Object used to operate the inverter.
Index
Sub-
index
Name
Type Property Unit Range
0x6040 -
Control word
U16
RW
-
-
In the event CM-11 Profile Sel is set to 1 (ES Device Profile (PDO3)),
this parameter is not supported.
The Bit composition below presents the bit command of the Control
Word.
Bit
Description
0
Switch on
1
Enable voltage
2
Disable quick stop
3
Enable operation
4
Ramp function generator disable
5
Ramp function generator stop
6
Ramp function generator zero
7
Reset fault
8
Halt
9
Reserved
10
Reserved
11~15
Reserved
The state of FSA (Finite State Automation) in the Chapter 6.1.1 by
changing the value of Control word into Bit information related with
Device operation command using the values of Bits 0~3 and Bit 7.
For example, Controlword must be 0XxxxF(xxxx xxxx xxxx 1111) to
become
“Operation Enable” FAS state in the table below (in the case
of No. 4 Transition).