No dehumidification. Compressor does not run but 

blower runs with fan switch AUTO and humidity control 
turned to ON.

1.  Defrost thermostat open, ambient temperature too low.
2.  Loose connection in compressor circuit.
3.  Defective compressor overload.
4.  Defective compressor or compressor run capacitor.

Blower runs with fan switch AUTO but compressor  

cycles on & off.

1.   Low ambient temperature and/or humidity causing unit
  to cycle through defrost mode.
2.  Defrost thermostat defective.
3.   Defective compressor overload.
4.   Defective compressor.

Blower does not run with fan switch in either position. 

Compressor runs briefly but cycles on and off.

1.  Loose connection in blower circuit.
2.  Obstruction prevents impeller rotation.
3.  Defective blower.
4.  Defective blower switch.

Evaporator coil frosted continuously, low  

dehumidifying capacity.

1.  Dirty air filter or air flow restricted.
2.   Defrost thermostat loose or defective.
3.  Low refrigerant charge.

If none of the above has fixed the issue, call  
technical support at 1-800-533-7533, Ext. 8459.

9. Service Parts List -  

Call your dealer or 1-800-533-7533.

Part No 

Description

4034011-02 

Evaporator

4034093 

Capillary Tubes

4028089 

 Compressor

1970010 

Compressor Relay 

4029510 

Filter/drier

4034109 

Condensor

4032196 

Impeller

4033032-03 

35mfd 370V Capacitor - Compressor

4033031-02 

5mfd 370V Capacitor - Impeller

4026221 

Leveling Foot

4031376 

Defrost Thermostat 

4027172 

Humidity Controller

4025560 

Fan Switch

SANTA FE ADVANCE2 OWNER’S AND INSTALLER’S MANUAL

6

Santa Fe Advance2 Installer’s & Owner’s Manual

11. Wiring Diagram

10. Accessory/Replacement Parts -

Call your dealer or order online.

4031062 

Filter MERV 8

4033036 

Filters 4-Pack, MERV 8

4033037 

Filters 12-Pack, MERV 8 

4028616 

Caster Kit

4033038 

Pump Kit 

4033039 

Duct Kit 

4026969 

10" Flex Duct 

4022126 

10" Flex Duct (Insulated) 

4020175 

Remote Dehumidistat

Summary of Contents for Advance2

Page 1: ...anta Fe Products com Designed for Basement and Crawlspace Dehumidification n High capacity n High efficiency n Environmentally friendly n Patent pending dual air distribution INSTALLER S OWNER S MANUAL P N 4034180 Serial No ________________________ Install Date ___________ Sold by Patent Pending Dual Air Distribution ...

Page 2: ...ned while it is plugged in Do not sit or stand on the unit or use as a shelf or table Before leaving the unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is designed to be installed indoors only Read the installation operation and maintenance instructions carefully before installing and using this un...

Page 3: ...n 3 Mount 4 above drain 4 Do not install the Santa Fe Advance2 with the exhaust of the unit within 1 of a wall or obstruction Do not place the unit near open water 4 2A No Ducting Figure 1 The simplest installation is to place the Santa Fe Advance2 with no ducting To ensure optimal performance the air inlet and the outlet of the unit must be at least 1 from walls and other obstructions to air flow...

Page 4: ...apter provided or by using a male 3 4 NPT PVC pipe Using either option care must be taken installing adaptor to the drain port Use standard condensate drain routing practices outlined when routing the drain line Be sure the hose is not kinked or otherwise restricted so that water can pass through it Improper hose installation may result in water leakage To increase the efficiency of the unit posit...

Page 5: ...move heat and moisture from incoming air and add heat to the air that is discharged Hot high pressure refrigerant gas is routed from the compressor to the condenser coil The refrigerant is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit The refrigerant liquid then passes through a filter drier and capillary tubing which cause the refrigerant press...

Page 6: ...ifying capacity 1 Dirty air filter or air flow restricted 2 Defrost thermostat loose or defective 3 Low refrigerant charge If none of the above has fixed the issue call technical support at 1 800 533 7533 Ext 8459 9 Service Parts List Call your dealer or 1 800 533 7533 Part No Description 4034011 02 Evaporator 4034093 Capillary Tubes 4028089 Compressor 1970010 Compressor Relay 4029510 Filter drier...

Page 7: ...a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the applicable warranty period The...

Page 8: ...1 800 533 7533 www santa fe products com ...

Reviews: