n
No dehumidification. Compressor does not run but
blower runs with fan switch AUTO and humidity control
turned to ON.
1. Defrost thermostat open, ambient temperature too low.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor or compressor run capacitor.
n
Blower runs with fan switch AUTO but compressor
cycles on & off.
1. Low ambient temperature and/or humidity causing unit
to cycle through defrost mode.
2. Defrost thermostat defective.
3. Defective compressor overload.
4. Defective compressor.
n
Blower does not run with fan switch in either position.
Compressor runs briefly but cycles on and off.
1. Loose connection in blower circuit.
2. Obstruction prevents impeller rotation.
3. Defective blower.
4. Defective blower switch.
n
Evaporator coil frosted continuously, low
dehumidifying capacity.
1. Dirty air filter or air flow restricted.
2. Defrost thermostat loose or defective.
3. Low refrigerant charge.
If none of the above has fixed the issue, call
technical support at 1-800-533-7533, Ext. 8459.
9. Service Parts List -
Call your dealer or 1-800-533-7533.
Part No
Description
4034011-02
Evaporator
4034093
Capillary Tubes
4028089
Compressor
1970010
Compressor Relay
4029510
Filter/drier
4034109
Condensor
4032196
Impeller
4033032-03
35mfd 370V Capacitor - Compressor
4033031-02
5mfd 370V Capacitor - Impeller
4026221
Leveling Foot
4031376
Defrost Thermostat
4027172
Humidity Controller
4025560
Fan Switch
SANTA FE ADVANCE2 OWNER’S AND INSTALLER’S MANUAL
6
Santa Fe Advance2 Installer’s & Owner’s Manual
11. Wiring Diagram
10. Accessory/Replacement Parts -
Call your dealer or order online.
4031062
Filter MERV 8
4033036
Filters 4-Pack, MERV 8
4033037
Filters 12-Pack, MERV 8
4028616
Caster Kit
4033038
Pump Kit
4033039
Duct Kit
4026969
10" Flex Duct
4022126
10" Flex Duct (Insulated)
4020175
Remote Dehumidistat