WARNING!
4.2 Electrical Requirements
The Santa Fe Advance2 plugs into a common grounded outlet
on a 110-120 VAC 15-Amp circuit. While operating, it draws
less than 6 amps @ 80°F, 60% RH and less than 5.5 amps @
75°F, 50% RH. Use of a ground fault circuit interrupter (GFCI)
protected circuit is recommended. The unit should not be used
in areas prone to flooding.
4.3 Installing Feet
Included with your Santa Fe
Advance2 are four leveling feet.
It is important to level the unit
for proper draining.
Installing Leveling Feet
See Figure 2 for installing leveling feet.
1. Lay down a protective pad (pillow, blanket, etc.).
2. Carefully turn unit onto side opposite drain port.
3. Align leveling foot shaft with one of the four threaded
hole locations as shown in Figure 2.
4. Screw each leveling foot in ten revolutions.
5. Carefully bring unit to upright position.
6. Level unit for proper water drainage.
7. Wait 10 minutes before operating.
CAUTION!
Note: Operating the unit immediately after bringing it to an
upright position can possibly damage the compressor. A short
amount of time is needed (10 minutes) to allow the oil to
return to it’s reservoir for lubrication.
CAUTION!
For proper drainage, the
unit must be mounted so the drain outlet is at
least 4" above the floor drain, and must be fully
supported under the base.
4.4 Condensate Water Removal
The Santa Fe Advance2 drains via a gravity system - it is not
able to push condensate (water) uphill. The drain hose must
run downhill toward the drain location. Condensate can be
drained by using the 5/8" clear hose and adapter provided,
or by using a male 3/4" NPT PVC pipe. Using either option,
care must be taken installing adaptor to the drain port. Use
standard condensate drain routing practices outlined when
routing the drain line.
Be sure the hose is not kinked or otherwise restricted so that
water can pass through it. Improper hose installation may
result in water leakage.
To increase the efficiency of the unit, position the hose to
create a “trap” as shown in Figure 3. By creating a trap, it will
hold a small amount of water. Position the trap on the hose
approximately 12" to 20" away from the unit. Check hose
regularly to ensure it is clear and water is draining properly.
If floor drain is not
easily accessible, a
condensate pump
kit with a 20' hose is
available. Contact your
dealer or order online if
you are interested in ordering the pump.
CAUTION!
Remove compressor shipping
tie from the unit. Failure to remove shipping tie
will cause excess vibration to be transmitted to
the frame.
5. Ducting
5.1 Duct Kit (P/N 4033039)
A factory designed outlet duct kit can be purchased to
accept 10" ducting to both outlets of the Santa Fe Advance2.
Contact your dealer or order online.
6. Operation
6.1 Humidity Control Adjustment
The humidity control is an adjustable switch that closes when
the relative humidity of the air in which it is located rises to
the dial set point. It opens when the RH drops 4 to 6% below
the set point.
Approximate Humidity Levels Per Setting:
“Drier” 20% to 30% Relative Humidity
“Normal” 45% to 55% Relative Humidity
(Recommended)
“Humid” 80% to 90% Relative Humidity
SANTA FE ADVANCE2 OWNER’S AND INSTALLER’S MANUAL
4
Santa Fe Advance2 Installer’s & Owner’s Manual
Figure 1: Four leveling feet
Figure 2: Insert leveling feet
in locations
4031882
Auto
On