![Sanken SAMCO-NS Series Instruction Manual Download Page 58](http://html1.mh-extra.com/html/sanken/samco-ns-series/samco-ns-series_instruction-manual_3998598058.webp)
Water Supply Function
F34xx
-57-
Water Supply Function
F34xx
Code
Function Name
Data Content
Setting
resolution
Factory
preset
3401
Water supply mode
Selection
0
:
Water supply function disabled
1
:
Single Pump Mode
1
0
3402
Lower limit range
continued time T1
0.1
~
10
Min.
0.1min.
5
3403
Sleep wake up ratio
K
30
~
95
%
1%
50
3404
Sleep wake up
Judgement time Tp
0.1
~
10
min.
0.1min.
5
3405
Pressure command
Pref
0
~
9.999MPa
0.001MPa
0
3406
Analog feedback upper
pressure limit
0
~
±9.999MPa
0.001MPa
0
3407
Analog feedback lower
Pressure limit
0
~
±9.999MPa
0.001MPa
0
3408
Upper pressure value
limit Ph
0.001
~
9.999MPa
0.001MPa
1
3409
Lower pressure value
limit PL
0
~
9.999MPa
0.001MPa
0
3410
The slip of pressure in
Acceleration
/Deceleration
0.001
~
9.999MPa
0.001MPa
0.1
3411
Allowed deviation on
Motor switching
0.0-20.0%
0.1%