![Sanken SAMCO-NS Series Instruction Manual Download Page 53](http://html1.mh-extra.com/html/sanken/samco-ns-series/samco-ns-series_instruction-manual_3998598053.webp)
-52-
Code
Function Name
Data Content
Setting
resolution
Factory
preset
3011
PID1 operation polarity
switching
1
:
Command value-feedbakck value
2
:
Feedback value-command value
1
1
3012
PID1 gain polarity switching
1: The positive or negative deviation indicates the
same gain
2: The positiveor negative deviation indicates the
different gain
1
1
3013
PID1 command value
gain
0
~
50
0.01
1
3014
PID1
feedback value
gain
0
~
50
0.01
1
3015
PID1 control proportional
gain( negative F3012=2
)
0
~
100
0.01
0.1
3016
PID1 control integral time
(
negative
:
F3012=2
)
0.01
~
100
sec.
0.01
sec.
0.1
3017
PID1 control command value
0
~
6000
0.1
0
3018
PID1 control feedback value
(
communication function
)
0
~
6000
0.1
0
3019
Frequency corresponding to
PID1 control max. command
value
0
~
600Hz
0.01Hz
60
3101
PID2
command value
Input switching
1: Frequency
2: External analog VRF voltage
(
0
~
5V
)
3: External analog VRF voltage
(
0
~
10V
or potentiometer
)
4: External analog V/I voltage
(
0
~
5V
)
5: External analog V/I voltage
(
0
~
10V
or potentiometer
)
9: External analog V/I current
(
4
~
20mA
)
11: Function code setting
(
F3117
)
1
0