-55-
Code
Function Name
Data Content
Setting
resolution
Factory
preset
3119
Frequency corresponding
to PID2 control max.
command value
0
~
600Hz
0.01Hz
60
3123
PID start mode seleciton
1
:
Direct input mode
2
:
Condition input mode
1
1
3124
PID end mode selection
1
:
Direct end mode
2
:
Condition end mode
1
1
3125
PID end setting value
1
~
100%
(
upper frequency limit standard
)
0.1%
20
3127
PID feedback signal
abnormal detection time
0
:
Only warning
0.01
~
119.99
sec.
120
:
No abnormal detection
0.01
sec.
2
3201
PID control action selection
0
:
Open loop control
1
:
PID1 control
2
:
PID2 control
4
:
External terminal switching PID control
5
:
Timing switch PID control
1
0
3203
External PID control
selection
0
:
No external PID control
1
:
PID1 external control
2
:
PID2 external control
4
:
PID1 and PID2 external control
1
0
3204
External PID operation
mode selection
1
:
Operation interlock with Inverter operation
2
:
PID output after power input
3
:
PID output controled by external terminals
1
1
3205
PID constitution selection 0:without command value addition calculation
1:with command value addition calculation
1
0
3206
Command value addition
Calculation
PID
control
gain
0.01
~
100
0.01
1
3207
PID1/PID2 switching time
0.1
~
6000
min.
0.1
min.
0.1
3301
Reading PID1
command
Value
Ready only
1
---
3302
Reading
PID1
feedback
Value
Ready only
1
---