SEC1000 FIRE ALARM CONTROL PANEL
Page
17
of 24
Specific c&e
In this section, the Causes can apply to specific devices by entering their assigned addresses.
Maximum of 5 points can be set at one time. Here the meaning of its c&e rule is only when all
the points set in the conditions are active, the outputs could take place.
5.2.4 Disable/test functions
Besides the disable/test functions that can be carried out at access level 2, there are some
other tests designed specially for the convenience of commissioning by authorized personnel
at access level 3. They are point test, module start/stop and duplicate address check.
Check duplicate address
This function helps you to locate detector/module with duplicate addresses on the loop.
When ‘Check’ clicked, it starts checking and the buttons are of no effect during the period.
When complete, all duplicate addresses will be shown as below.
Point test
This function allows you to view the analogue status of any addressable point in real time.
When selected, you will be prompted to enter the specific address of the device you want to
put into test:
Enter the target point and press OK to start the point test:
Note
: It is commonly used for
analyzing and locating faults, it will
not exit until a manual operation or
an event present, thus long time
use is not recommended.