SEC1000 FIRE ALARM CONTROL PANEL
Page
18
of 24
Module start/stop
This function allows you to trigger or stop an output type module to check the module and its
following device are working correctly.
When selected, all the addresses of preregistered modules with their device type will be listed
to be chosen from.
It provides an intuitive way for device commissioning individually.
5.2.5 Advanced functions
Besides some essential system configurations mentioned above, this ADVANCE category
provides supplementary functions for system commissioning including loop learn, data
load/backup, file reset and update of the system.
Loop learn
This function activates the panel’s automatic loop learn facility. As it prompts below, the loop
learn process may take about 120s and it cannot be stopped during the period.
When the auto-learn completes successfully, a comparison between the loop learn result and
the initial data will be given. And as it prompts, selecting Confirm will get entry to the
detector/module setup window with the Reg and Product Type data overwritten by the new
auto-learned data, which means the previous system configuration will be changed. So take
care about this before you continue with it. See the picture below.
Additionally, other attributes about the device will be set as default settings, for example, the
devices will be all assigned to zone 1 which can be modified as designed later.
The curve indicates the change of smoke
density in the no.47 smoke detector
during the test. Here, the background
value, alarm value and drift value only
apply to smoke detector. Press Exit to
stop at any time.