SEC1000 FIRE ALARM CONTROL PANEL

Page

22

of 24

7.2 Troubleshooting
Solution of all suspected faults MUST only be carried out by suitably qualified technical engineers.

Problem

: apply power to the panel but the LCD display is off and panel does not work.

Possible reason and solution

: check whether the cable is properly connected between the

CB-Board and the MB-Board; Check if the POWER indicator on the front panel is on, otherwise
something is wrong with the P.S.E that the manufacturer should be informed.

Problem

: both mains fault and battery fault are reported.

Possible reason and solution

: It may be due to the reason that the mains is in fault condition

while battery is at low voltage.

Problem

: a fault of loop open is reported.

Possible reason and solution

: check if the connector to the terminal of Loop Out or Loop In

is loose; Check if the circuit between Loop Out and Loop In exists an interruption.

Problem

: a fault of loop short is reported.

Possible reason and solution

: check if the polarized terminals of Loop Out and Loop In are

connected right, that is, ensure the signal from Loop Out (+) is not back to Loop In (-) by
mistake but to Loop In (+); Check if a short circuit exists on the loop and repair.

Problem

: alarm sounders cannot be activated when a fire signal is generated.

Possible reason and solution

: read the specific fault message regarding the sounders and

repair; Make sure sounders are powered by 24V; Check the cause and effect configuration
about sounders activation.

Problem

: the F.A.Out, or the S.C.Out is reported fault.

Possible reason and solution

: ensure that a 47K EOL resistor is well connected to each of the

two ports; Check if a short circuit exists on the port and repair.

Summary of Contents for SEC1000

Page 1: ......

Page 2: ...imum loop cable length recommendations 8 3 8 Other terminal connections 8 4 Indications and Controls 9 4 1 LED indicators 9 4 2 Button controls 10 4 3 Zone Indicators 11 5 Commissioning and Programmin...

Page 3: ...loop of 120 addressable points and expansion capabilities It is compatible with other peripherals made by Sanjiang with its own protocol 2 2 Technical Specifications Power supply Mains supply 230VAC...

Page 4: ...n rate 9600 bps Recommended type of cable Unscreened twisted pair 1mm2 Transmission distance 1000m Cable diameter 1mm2 2 5mm2 CAN Max number of panels 20 Transmission rate Optional 10K 20K 50K and 100...

Page 5: ...refer to the separate manual of PMC_01 and the datasheet of Switching Power Supply for more details The P S E is an integrated unit that provides power both for the panel and the backup rechargeable...

Page 6: ...C1000_COM PMC_01 LSP 75 24 ADJ TB4 LED TB3 DC TB2 AC TB1 AC TB5 Red Black Red Red Black Red Red Black Black Red Black Yellow green Blue Brown RS485 3 3 Mounting the chassis to the wall The panel can b...

Page 7: ...0V 10A L N Red Black Red Black Red Red Black Black Yellow green Blue Brown To Battery 3 5 Battery connection For this single loop system 2 12V 7Ah sealed lead acid batteries are used as per the calcul...

Page 8: ...Loop In and Loop Out terminal block on the MB Board It should be noted when the loop is in class B connection the terminal LOOP INPUT on MB Board is not available Means to limit the consequences of sh...

Page 9: ...meter Typical Resistance 1 0mm2 18 1 ohm km 1 5mm2 12 1 ohm km 2 5mm2 7 41 ohm km 3 8 Other terminal connections 1 F A Out short for Fire Alarm Output When there is a general fire the output is activa...

Page 10: ...d POWER FAULT Lit yellow when the panel s mains power battery or charger is in fault condition SYSTEM FAULT Lit yellow when the panel is unable to provide mandatory functions POWER Lit green to show t...

Page 11: ...access level 2 3 Press again to resound the sounders previously silenced Silences the panel s internal buzzer COPY Copies the content of text selected currently PASTE Pastes the content of text copie...

Page 12: ...ompletion of all the installation and connection work It includes registering and test of detectors and modules setup of the zone indication and control panel C E programming and etc All these functio...

Page 13: ...ion rate The number of each panel should be different There are 4 transmission rates 10K 20K 50K 100K Some factors like the total number of network panels the transmission distance of the system and t...

Page 14: ...ing function in order to avoid displaying confusion or communication error try to configure and register different zones on different networking panels Detector module setup All detectors and modules...

Page 15: ...ct Type are kept the same as detectors Refer to the Annex device type list for all the Device Type provided in this system The Zone refers to where a device belongs in the protected premises It repres...

Page 16: ...g In the event of a fire a default output of sounders will be activated Besides this outputs of specified modules can be set here as per requirements from the client specifier Click by the USB mouse o...

Page 17: ...e For the function of overriding delays by activating any MCP in the system it refers to the delay which is running If the MCP used to override the delays is involved in another c e rule with a time d...

Page 18: ...hey are point test module start stop and duplicate address check Check duplicate address This function helps you to locate detector module with duplicate addresses on the loop When Check clicked it st...

Page 19: ...prompts below the loop learn process may take about 120s and it cannot be stopped during the period When the auto learn completes successfully a comparison between the loop learn result and the initi...

Page 20: ...ata backup Take the prompt as reference Load data from U disk This function will load the configuration file from U disk to the panel s flash and overwrite the panel s existing data So this function m...

Page 21: ...rating as the prompt says will complete 5 2 6 View system and software version info The system information as well as the version of each processor with program can be read through the corresponding m...

Page 22: ...tor or a manual call point is typically 0 001A or 1mA while that of a input output modules or Intelligent Sounder Beacon is 0 008A or 8mA IRout is the alarm output current of the panel s three relays...

Page 23: ...son and solution check if the connector to the terminal of Loop Out or Loop In is loose Check if the circuit between Loop Out and Loop In exists an interruption Problem a fault of loop short is report...

Page 24: ...int MCP Fire Hydrant Call Point HydrCP Sounder Visual Indicator Sounder Strobe SoundStro Sounder Sounder Visual Alarm Strobe Strobe Alarm Bell Alarmbell Conventional Optical Detector ConvOptD Conventi...

Page 25: ...DelugeVal Generator Generator Stabilized Pressure Pump PressPump Fire Pump FirePump Foam Pump FoamPump Water Pump WaterPump Air Conditioner Air con Fire Emergence Evacuation Broadcast BCST Fire Emerg...

Page 26: ...SEC1000 FIRE ALARM CONTROL PANEL...

Reviews: