11
4. ELECTRIC CONNECTION
WARNING: before inspection or repair, make sure the unit is disconnected from the main electrical supply
(use the disconnect switch).
Single-phase voltage : 230V 50 Hz + earth
Conform to NF C 15-100 norm
Cabinet fan electrical characteristics:
CAB-PLUS
125
CAB-PLUS
160
CAB-PLUS
250
CAB-PLUS
315
Power max (Hs / Ls)
70/30W
100/33W
245/170W
310/160W
Intensity max (Hs / Ls)
0.3/0.2A
0.4/0.3A
1.1/1.0A
1.4/1.2A
Dephasing capacitor
2µF
3.5µF
5µF
15µF
Voltage drop capacitor
3µF
4.5µF
13µF
15µF
Standard wiring
CAB-PLUS 125 et 160
CAB-PLUS 250
CAB-PLUS 315
Wiring with disconnecting switch (all sizes)
Wiring with circuit-breaker (all sizes)
Speed choice
HS: see diagram
(Black wire on L3)
LS:to reverse white en
black
(White wire on L3)
Bl
ue
Wh
ite
Gr
een/
Ye
llo
w
Bl
ac
k
HS
N
M
~
50 Hz
G
re
en/
Y
el
low
1 2
M
~
3
Bl
ue
C2
W
hi
te
Bl
ac
k
50Hz
Ph
N
230V~
LS
HS
B
la
ck
C1
Br
ow
n
G
re
en/
Y
el
low
1 2
M
~
3
Bl
ue
Green
C1
C2
W
hi
te
Bl
ack
50 Hz
Ph
N
230V~
LS
HS
Yellow
Br
ow
n
G
reen/
Y
el
low
1 2
M
~
3
B
lue
Black
Brown
C1
C2
Bro
w
n
Bl
ack
50Hz
Ph
N
230 V~
LS
HS
M
~
4
3
6
5
2
1
8
7
50 Hz
Ph
N
230 V~
LS
HS
2
4
6
8
TOP
2. PRODUCT PRESENTATION
Fan casing manufactured from heavy gauge galvanized steel sheet.
Circular duct connection flanges with integrated rubber air seal.
Single inlet fan.
In line horizontal discharge.
Standard version, 25mm thickness of fireproof fiberglass insulation version (50mm thickness of
fireproof fiberglass insulation version on request).
Possibility to be equipped with a G4 filter.
Motors:
o
CAB-PLUS 125 and 160: IP44 motor with single-phase external rotor 230V, 50 Hz, class B, 2
speeds.
o
CAB-PLUS 250: IP20 single-phase asynchron motor 230V, 50 Hz, class B, 2 speeds.
o
CAB-PLUS 315: IP55 single-phase asynchron motor 230V, 50 Hz, class F, 2 speeds.
o
Motors with incorporated thermal protection with non-automatic resetting.
3. INSTALLATION
3.1 Dimensions and weights
3.2 Installation
The cabinet fan must be fixed on a plan support by the holes foreseen. Installation on anti-vibration mounts
and connection with flexible sleeves are recommended.
Access to the filter and to the motor fan is possible thanks to the cover: to be foreseen enough room, at least
C dimension of the cabinet for servicing and maintenance operations.
The aeraulics installation of the cabinet and its ventilation duct must achievement must satisfy to the technical
conditions defined on DTU 68-2.
If the cabinet fan is installed in or close to a place equipped with a boiler or another type of combustion device,
appropriate precautions shall be taken to avoid any gas o smoke exhaust coming from evacuation pipe of gas
device (boilers, …) or any fire devices (chimney, stove, …) inside the room.
E
B
G H
F
J
A
C
A
B
C
ØD
E
F
G
H
J
CAB-PLUS 125
340
330
210
125
93
415
364
350
250
7
CAB-PLUS 160
406
468
235
160
129
490
502
482
360
13
CAB-PLUS 250
490
488
364
250
178
630
530
514
400
20
CAB-PLUS 315
537
544
380
315
194
652
587
565
470
24
Dimensions in mm
Weights
(kg)
Sizes
Cabinet fan
Fixations