S&C Instruction Sheet 1011-510
17
Ungrounded Wye Shunt Reactors
At this point, you can test the faceplate LEDs and buttons. See Figure 2 on
page 10.
A. Press
the
POWER SUPPLY
button. If the control has power, the button will light
up (green). If the
LOCKOUT INDICATOR
or
ALARM INDICATOR
LED turns
ON, press the corresponding
RESET
button to clear it.
B. Press
the
ENTER
button to test the faceplate LEDs. All LEDs should turn ON
for 2 seconds.
C. Press
the
NEXT
button to scroll through the information on the LCD. (If password
protection is enabled, press the
NEXT
button again to start scrolling through
password values.) If the display is blank, see the Troubleshooting Instruction
Sheet 1011-550.