background image

   

S&C Instruction Sheet 1011-510

   

11

Grounded Wye Banks

Installation

Installation consists of several operations. The details of these operations, and the order 
in which they must be carried out, depend on the type of control device, and on local 
or customer codes, standards, and procedures. The following information is specifi c to 
BankGuard Plus Controls protecting 

grounded wye-connected capacitor banks

.

  The required fuse blocks and fuses are furnished with the control, and you must 
installthem. When you design the installation, be sure to provide adequate ventilation; 
the temperature near the control should not exceed 160°F. This is particularly important 
when the control is installed in a cabinet or when several controls are installed close 
together.

  To ensure that the control is not subjected to excess surges (ANSI Standard C37.90a), 
we recommend the following:

•  

Provide adequate shielding for the control-circuit wiring. Refer to the interconnection 
diagram furnished.

•  

For installations involving two or more grounded-wye capacitor banks in the same 
station, interconnect and ground their neutrals at a single point only. Also, to reduce 
inrush current and transient voltage disturbances, you may want to equip the capacitor 
bank switching devices with pre-insertion resistors or to provide current- limiting 
reactors.

  For a grounded wye-connected capacitor bank, the BankGuard Plus control requires 
three potential devices to monitor intermediate tap point voltages. The intermediate tap 
point for each phase of the bank should be located as follows:

• 

 

For capacitor banks with an even number of series groups per phase

, the number 

of series groups between the tap point and ground should equal the number of series 
groups between the tap point and the line.

• 

 

For capacitor banks with an odd number of series groups per phase

, the number of 

series groups between the tap point and ground should be one less than the number 
of series groups between the tap point and the line.

Step 1

  Read and make sure you understand the following warnings before you begin 

installatin or operate this equipment.

Ç

 WARNING

These instructions do NOT replace the need for utility operation standards. Any 
conflict between the information in this document and utility practices should be 
reviewed by appropriate utility personnel and a decision made as to the correct 
procedures to follow.

  Serious risk of personal injury or death may result from contact with electric 
distribution equipment when electrical isolation and grounding procedures are not 
followed. The equipment described in this document must be operated and main-
tained by qualified persons who are thoroughly trained and understand any hazards 
that may be involved. This document is written only for such qualified persons and 
is not a substitute for adequate training and experience in safety procedures for 
accessing high voltage equipment.

  This control is connected to capacitors operating at primary voltage levels. High 
voltage may be present in the wiring to the control or the control itself during cer-
tain failures of the capacitor bank wiring or system grounding, or due to a failure 
of the capacitor bank itself. For this reason, access to the control should be treated 
with the same safety precautions that would be applied when accessing other high 
voltage lines and equipment. Follow all locally approved safety procedures when 
working on or around this control.

  Do not energize the control power source entering the control enclosure until all 
wiring is complete.

Summary of Contents for BankGuard PLUS

Page 1: ...tion Checklist 4 In Shop Setup 4 Ungrounded Wye Banks Installation 5 Test the Control 10 Grounded Wye Banks Installation 11 Test the Control 13 Ungrounded Wye Shunt Reactors Installation 14 Test the C...

Page 2: ...nkGuard Plus Designate a location where you can easily retrieve and refer to this publication Warranty SPECIAL WARRANTY PROVISIONS The standard warranty contained in seller s standard conditions of sa...

Page 3: ...OTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion...

Page 4: ...e problems that can occur uring installation NOTE Although it is possible use the faceplate buttons and LCD for the initial setup of the control using the IntelliLink software makes the process faster...

Page 5: ...rds that may be involved This document is written only for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equipment...

Page 6: ...BankGuard Plus Control includes numbered terminal strips on the back of the enclosure for external control wiring connections See Figure 1 Table 1 and the electrical diagrams at the end of this instru...

Page 7: ...B1 11 Star voltage TB1 12 Star voltage return TB2 A 2nd Lockout O O O C TB2 B 2nd Lockout O O O C TB2 1 Chassis ground TB2 2 Lockout C C C O TB2 3 Lockout C C C O TB2 4 Lockout O O O C TB2 5 Lockout O...

Page 8: ...C 30 Volt Ampere Potential Device s to TB1 9 TB1 10 DB2 11 and TB2 12 phase voltage return Step 4 If necessary connect the potential devices or voltage transformers used for unbalance compensation If...

Page 9: ...e to ground voltage relationships for all but fault conditions The circuits connecting the potential devices voltage transformers to the BankGuard Plus Control must be free of variable loads variable...

Page 10: ...rmation on the LCD If password protection is enabled press the NEXT button again to start scroll ing through password values If the display is blank see the Troubleshooting Instruction Sheet 1011 550...

Page 11: ...ap point and ground should equal the number of series groups between the tap point and the line For capacitor banks with an odd number of series groups per phase the number of series groups between th...

Page 12: ...ircuit of the bank switch operator to TB2 4 and TB2 5 D The closing circuit of the bank switch operator to TB2 2 and TB2 3 E The control device power source 48 250 Vdc 100 240 Vac 50 or 60 Hz as appro...

Page 13: ...INDICATOR or ALARM INDICATOR LED turns ON press the corresponding RESET button to clear it B Press the ENTER button to test the faceplate LEDs All LEDs should turn ON for 2 seconds C Press the NEXT b...

Page 14: ...hazards that may be involved This document is written only for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equi...

Page 15: ...p 3 Step 3 If necessary connect the potential devices or voltage transformers used for unbalance compensation If the BankGuard Plus Control uses the optional unbalance compensation feature you must al...

Page 16: ...This insures that the monitored voltages accurately represent the magnitude and phase angle of the bus voltages Some possible errors affecting unbalance compensation are Differences in the effective...

Page 17: ...INDICATOR or ALARM INDICATOR LED turns ON press the corresponding RESET button to clear it B Press the ENTER button to test the faceplate LEDs All LEDs should turn ON for 2 seconds C Press the NEXT b...

Page 18: ...BankGuard Plus installation S C Electric Company supports the BankGuard Plus Control with a variety of communi cations hardware options S C SpeedNet Radio UtiliNet Radio Cellnet Radio Microwave Data...

Page 19: ...S C Instruction Sheet 1011 510 19 Installation and Connection Drawings...

Page 20: ...20 S C Instruction Sheet 1011 510 Installation and Connection Drawings...

Page 21: ...S C Instruction Sheet 1011 510 21 Installation and Connection Drawings...

Page 22: ...22 S C Instruction Sheet 1011 510 Installation and Connection Drawings...

Page 23: ...S C Instruction Sheet 1011 510 23 Installation and Connection Drawings...

Page 24: ...Printed in U S A...

Reviews: