![Samwontech TEMP1000 Series Communications Manual Download Page 8](http://html1.mh-extra.com/html/samwontech/temp1000-series/temp1000-series_communications-manual_3799368008.webp)
SAMWONTECH
1th Edition of TEMP1000_Series IM : Apr. 2014 Page 6 / 63
█
6 Pin connector wiring for RS232C interface
█
6 Pin connector wiring for RS485 interface
☞
Up to 31 slave TEMP1500 controllers can be connected to a master device by multi-drop networking.
☞
Make sure to install 200Ω(1/4W) resistor on Last Leg at both end of terminal Slave and Master(PC, PLC).
①
○
TEMP1500(COM2)
Master Station
Shielded Cable
TxD
②
RxD
③
SG
SHIELD
②
RD
③
TD
⑦
RTS
⑧
CTS
⑤
SG
RTX-
RTX+
SG
Master Station
Shielded Cable
TEMP1500(COM2)
TEMP1500(COM2)
①
RTX-
②
RTX+
③
SG
①
RTX-
②
RTX+
③
SG