7.12 DO CONFIG Group
DO CONFIG group consists of setting and information parameter D-Register related to establish RELAY number on
I/O board to generate signal and its sub setting for auxiliary Digital Output.
█ DO CONFIG setting and information D-Register
D-Reg.
Symbol
Descriptions
D1101~D1108
IS1.RLY~IS8.RLY
RELAY No.on I/O for INNER SIGNAL.
D1109~D1116
TS1.RLY~TS8.RLY
RELAY No.on I/O for TIME SIGNAL.
D1117~D1120
ALM1.RLY~ALM4.RLY
RELAY No.on I/O ALARM SIGNAL.
D1121~D1124
SA1.RLY~SA4.RLY
RELAY No.on I/O SEGMENT ALARM SIGNAL.
D1125~D1138
T1.RLY~T7.DYT
RELAY No.on I/O and DELAY TIME for ON/OFF SIGNAL.
D1139~D1154
DI1.RLY~DI16RLY
RELAY No.on I/O for DI SIGNAL.
DI1155~D1166
USER.RLY1~USER.RLY12
RELAY No.on I/O for MANUAL SIGNAL.
D1167
USER.RLY_ON/OFF
Switch “ON” the relay for the corresponding
number manually.
D1168~D1175
LOG1.RLY ~ LOG8.RLY
RELAY No.on I/O for LOGICAL SIGNAL
D1176,D1177
HOLD.RLY, HOLD.OPT
RELAY No.on I/O and OPERATION TIME for ON/OFF SIGNAL.
D1201,D1202
RUN.RLY,RUN.DYT
RELAY No.on I/O and DELAY TIME for RUN SIGNAL.
D1203,D1204
SOPN.RLY,SOPN.KPT
RLY No.on I/O and KEEP TIME for SENSOR-OPEN SIGNAL.
D1205,D1206
WAIT.RLY,WAIT.KPT
REALY No.on I/O and KEEP TIME for WAIT SIGNAL.
D1207, D1208
FIXTIMER.RLY,FIXTIMER.DEV
RELAY No.on I/O and DEVIATION for FIXTIMER SIGNAL
D1209, D1210
FIXTIMER.DLY,FIXTIMER.OPT
DELAY TIME and OPERATION TIME for FIXTIMER SIGNAL
D1211,D1212,D1213
UP.RLY,UP.DEV,
UP.DEVSEL
RELAY No.on I/O, DEVIATION and Operating conditions for
UP SIGNAL.
(Operating conditions 0:[TSP-NSP] ,1:[TSP-NPV])
D1214,D1215
SOAK.RLY,SOAK.KPT
REALY No.on I/O and KEEP TIME for SOAK SIGNAL.
D1216,D1217,D1218
DOWN.RLY,DOWN.DEV,
DOWN.DEVSEL
RELAY No.on I/O, DEVIATION and Operating conditions for
DOWN SIGNAL.
(Operating conditions 0:[TSP-NSP] ,1:[TSP-NPV])
D1219,D1220
1REF.RLY,1REF.DYT
RELAY No.on I/O and DELAY TIME for 1
st
Refrigerator oper.
D1221,D1222
2REF.RLY,2REF.DYT
RELAY No.on I/O and DELAY TIME for 2
nd
Refrigerator oper.
D1223,D1224
ERROR.RLY,ERROR.KPT
REALY No.on I/O and KEEP TIME for ERROR SIGNAL.
D1225,D1226,D1227
FEND.RLY,FEND.DLT
FEND.OPT
RLY No.on I/O, DELAY TIME, OPERATION TIME for
FIX-END SIGNAL.
D1228,D1229,D1230
PTEND.RLY,PTEND.DLT
PTEND.OPT
RLY No.on I/O, DELAY TIME, OPERATION TIME for
PROGRAM PTN-END SIGNAL.
D1231,D1232
UKEY.RLY,UKEY.OPT
RELAY No.on I/O for USER KEY SIGNAL.