NOVA541
- 58 -
※ Output Direction mode
Forward (FWD) : ON when alarm condition, OFF when alarm off
Reverse (REV) : OFF when alarm condition, ON when alarm off
※ The condition of Standby
Power On
Changing of Alarm Kind
Changing SP
4-6-1 Alarm Kinds
▪ Set the alarm type of Alarm1,2,3.
Symbol
Parameter
Setting range
Display
Unit
Default
ALT1
Alarm 1 Type
Table 4. Types of Alarm
Always
ABS
AH.F
ALT2
Alarm 2 Type
ALT3
Alarm 3 Type
4-6-2 Alarm point
▪ Set the alarm point of Alarm1,2,3.
Symbol
Parameter
Setting range
Display
Unit
Default
AL1
Alarm 1 Set Value
EU(-100.0 ~ 100.0%)
Alarm type is
not a Dev.
EU
EU(100.0%)
AL2
Alarm 2 Set Value
AL3
Alarm 3 Set Value
4-6-3 High/Low Deviation Alarm
▪ Set high and low deviation of Alarm1,2,3.
Symbol
Parameter
Setting range
Display
Unit
Default
AL1.H
Alarm 1 Set High Deviation
EUS(-100.0 ~ 100.0%)
Alarm type is
a Dev. Type
EUS
EUS(0.0%)
AL1.L
Alarm 1 Set Low Deviation
AL2.H
Alarm 2 Set High Deviation
AL2.L
Alarm 2 Set Low Deviation
AL3.H
Alarm 3 Set High Deviation
AL3.L
Alarm 3 Set Low Deviation