NOVA541
- 35 -
4-1-1 Input type
▪ Select the input type to use, considering sensor type and input range.
▪ Refer to Table 1 as a guide of sensor type and input range.
Symbol
Parameter
Setting range
Display
Unit
Default
IN-T
Input Sensor Type
Table1
Always
ABS
TC.K1
4-1-2 Temperature Unit (UNIT)
▪ Choose a temperature unit between “℃” and “℉”.
▪ Changing IN-U, the temperature range will be converted automatically.
▪ IN-U parameter appears only when IN-T is one of TC or RTD group.
Symbol
Parameter
Setting range
Display
Unit
Default
IN-U
Input Unit
℃, ℉
IN-T = TC
IN-T = RTD
ABS
℃
4-1-3 Input range
▪ Setting the high and low limits of the sensor input range
◦ TC, RTD Input
When a RANGE CODE is selected, the range is set as Table 1. The range can be modified
with IN.RH and IN.RL parameters. Decimal point position cannot be change by these
parameters.
◦ DCV, mV Input
The input range can be determined by selecting a RANGE CODE and adjusted by modifying
the parameters, IN.RH, IN.RL.
Symbol
Parameter
Setting range
Display
Unit
Default
IN.RH
Input Range High
Table 1
( IN.RH > IN.RL )
Always
EU
EU(100.0%)
IN.RL
Input Range Low
EU(0.0%)
Setting Example
▪ When the range code TC.K1( -200~1370℃) is selected and setting IN.RL = -100 and IN.RH =
500, the input is limited in the range of -100~500℃.