NOVA541
- 34 -
4. Functions
4-1. Sensor input (G.IN)
Input Type (IN-T) : Thermocouple (TC), Resistive thermal detector (RTD), DC volt (DCV)
In case of TC or RTD, the sensor type and temperature range should be selected.
In case of DCV, the input types are classified with the range of input voltage.
Table 1. Input types
GROUP
DISPLAY
INPUT TYPE
RANGE(℃)
RANGE(℉)
TC
TC.K1
K1
-200 ~ 1370
-300 ~ 2500
TC.K2
K2
-200.0 ~ 1370.0
-300.0 ~ 1900.0
TC.J
J
-200.0 ~ 1200.0
-300.0 ~ 1900.0
TC.E
E
-200.0 ~ 1000.0
-300.0 ~ 1800.0
TC.T
T
-200.0 ~ 400.0
-300.0 ~ 750.0
TC.R
R
0.0 ~ 1700.0
32 ~ 3100
TC.B
B
0.0 ~ 1800.0
32 ~ 3300
TC.S
S
0.0 ~ 1700.0
32 ~ 3100
TC.L
L
-200.0 ~ 900.0
-300 ~ 1600
TC.N
N
-200.0 ~ 1300.0
-300 ~ 2400
TC.U
U
-200.0 ~ 400.0
-300.0 ~ 750.0
TC.W
W
0 ~ 2300
32 ~ 4200
TC.PL
Platinel Ⅱ
0.0 ~ 1390.0
32 ~ 2500
TC.C
C
0 ~ 2320
32 ~ 4200
RTD
PTA
PTA
-200.0 ~ 850.0
-300.0 ~ 1560.0
PTB
PTB
-200.0 ~ 500.0
-300.0 ~ 1000.0
PTC
PTC
-50.00 ~ 150.00
-148.0 ~ 300.0
PTD
PTD
-200 ~ 850
-300 ~ 1560
JPTA
JPTA
-200.0 ~ 500.0
-300.0 ~ 1000.0
JPTB
JPTB
-50.00 ~ 150.00
-148.0 ~ 300.0
DCV
2V
0.4 ~ 2.0V
0.400 ~ 2.000 V
5V
1 ~ 5V
1 ~ 5 V
10V
0 ~ 10V
0 ~ 10 V
20MV
-10 ~ 20mV
-10 ~ 20 ㎷
100MV
0 ~ 100mV
0 ~ 100 ㎷
▪ Display range : -5% ~ +105% of above range