NOVA541
- 24 -
1-5. Initial parameter setting sequence
2. Sensor type (IN-T) set
1. Wiring and Power ON
3. Input Range (IN.RH, IN.RL)
4. Out Type (OUT1, OUT2)
6. Event Port (EV1, 2 ,3)
5. Alarm(AL1, 2 ,3), IS1,IS2
7. PID RP(Reference point)
8. SP(Setting point)
9. Auto tuning
10. Test Run after auto tuning
After wiring according to installation manual, power ON
Set the sensor kind first of all and most
parameters will be reset at this time accordingly.
Adjust the temperature range, considering the
processing conditions.
사용하는 제어출력에 알맞은 출력종류를 설정합니다.
Set Alarm, Inner signal
.
Select signal type for EV1, 2, 3
Set the reference points (RP) considering the zones
and corresponding PID sets. For deviation PID, set
RDV and AT-G for 4.PID
Set a temperature (SP) for auto-tuning
Execute auto tuning. When using multiple PID zone,
auto tuning is necessary at each zone respectively.
.
After auto tuning, execute test runs at several set
points.