Wiring
The power cable is not supplied with air conditioner.
For power cable, use the grade H07RN-F materials in 3Φ system.
Ssc(MVA) : 3.5(Type of outdoor unit A), Ssc(MVA) : 3.8(Type of outdoor unit B and C)
The power cable is not supplied with air conditioner.
For power cable, use the grade H05RN-F materials in 1Φ system.
This equipment complies with "IEC 61000-3-12".
The Power cable is not supplied with the heat pump.
For power cable, use the grade H07RN-F materials in 1
Φ
system.
If you connect Backup Heater at separated power cable, you can reduce wire size. (Please refer to indoor unit installation manual)
Type of outdoor unit
Outdoor
Power supply
Power cable
MAX. LENGTH
Type GL
mm²,wires
m
A
A
RC090MHXEA
1Φ, 220-240V, 50Hz
4.0/3
<10m
30
6.0/3
10m<L<20m
B
RC120MHXEA
1Φ, 220-240V, 50Hz
4.0/3
< 10m
30
6.0/3
10m<L<20m
C
RC140MHXEA
RC160MHXEA
1Φ, 220-240V, 50Hz
4.0/3
< 10m
40
6.0/3
10m<L<20m
Power Cable Specifications
Single Phase
3 Phase
Type of outdoor unit
Outdoor
Power supply
power cable
MAX. LENGTH
Type GL
mm²,wires
m
A
A
3Φ, 380~415V, 50Hz
1.5/4
<10m
20
2.5/4
10m<L<20m
B
RC120MHXGA
3Φ, 380~415V, 50Hz
1.5/4
<10m
20
2.5/4
10m<L<20m
C
RC140MHXGA
RC160MHXGA
3Φ, 380~415V, 50Hz
1.5/4
<10m
20
2.5/4
10m<L<20m
Indoor Unit
Load
Power supply
Power cable
MAX. LENGTH
Type GL
mm²,wires
m
A
MIM-E03A
No Heater
(Water Pump, Valve, Wired RMC)
1Φ, 220-240V, 50Hz
1.5 / 3
<10m
10
2.5 / 3
10m<L<20m
10
Booster Heater (3kw)
4.0 / 3
<10m
20
6.0 / 3
10m<L<20m
20
Booster Heater (~3kw)
+ Backup Heater (~3kw)
6.0 / 3
<10m
40
8.0 / 3
10m<L<20m
40