25
ENGLISH
When it is required to change the default pre-pressure of the expansion vessel(1 bar), keep in mind the following guidelines:
Use only dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will lead to malfunction of the system.
Therefore, the pre-pressure should only be adjusted by a licensed installer.
Installation height
difference
(a)
Water volume
< 220 Litres
> 220 Litres
<7m
No pre-pressure adjustment required.
Actions required:
• Pre-pressure must be decreased, calculate
according to
“Calculating the pre-pressure of the expansion
vessel”.
• Check if the water volume is lower than
maximum allowed water volume
>7m
Actions required:
• Pre-pressure must be increased, calculate the
appropriate value following by “Calculating
the pre-pressure of the expansion vessel”.
• Check if the water volume is lower than
maximum allowed water volume
Expansion vessel of the unit too small
for the installation.
(a) Installation height difference: height difference(m) between the highest point of the water circuit and the indoor unit.
If the unit is located at the highest point of the installation, the installation height is considered 0m
.
Calculating the pre-pressure of the expansion vessel
The pre-pressure(Pg) to be set depends on the maximum installation height difference(H) and is calculated as below:
Pg=(H/10+0.3) bar
2.5
2.0
1.5
1.0
0.5
0.0
150
200
250
300
350
Total water volume(ℓ)
Pr
e-
pr
es
su
re
(b
ar
)
Operation range
Setting capacity and pre-pressure of the expansion vessel
Summary of Contents for RC***MHXGA
Page 41: ...41 Memo ...
Page 42: ...42 Memo ...
Page 43: ...43 AA Memo ...
Page 44: ... EEE Yönetmeliğine Uygundur This EEE is compliant with RoHS ...