ENGLISH
37
Trouble shooting
Trouble shooting
No.
LED Display
Displayed
PCB Assy
Meaning
Remarks
Error Code
Red Green
Yellow
-
MAIN/INVERTER
Normal operation
(MAIN : Indoor
Outdoor : Green ON)
(INVERTER : MAIN PCB
INVERTER PCB : Green ON)
-
1
MAIN
Unit quantity miss matching between indoor and
outdoor.
Check indoor quantity setting in
outdoor.
E201
2
MAIN/INVERTER
Abnormal state, no communication between Indoor
and Outdoor Main PCB
Check electrical connection and setting
E202
3
MAIN/INVERTER 1min. Time out of communcation error(Main
Inverter) Check electrical connection and setting
E203
4
MAIN
Outdoor temp sensor error
Check Outdoor sensor Open/Short
E221
5
MAIN
Cond. temp sensor error
Check Cond. sensor Open/Short
E231
6
MAIN
Discharge temp sensor error
Check Discharge sensor Open/
Short
E251
7
MAIN
OLP Sensor Error
Check OLP sensor Open/Short
E320
8
MAIN
Detection of Outdoor Freezing when Comp. Stop
Check Outdoor Cond.
E403
9
MAIN
Protection of Outdoor Overload when Comp. Stop Check Comp. when it start
E404
10
MAIN
Discharge temperature of a compressor in an
outdoor unit is overheated.
E416
11
MAIN
Heating operation is not available since the outdoor
air temperature is over 35°C.
Heating
E440
Cooling operation is not available since the outdoor
air temperature is lower than -5°C.
Cooling
E441
12
MAIN/INVERTER Outdoor unit BLDC Fan 1 or Fan 2 error
FAN1 error
E458
FAN2 error
E475
13
MAIN/INVERTER Comp. Starting error
E461
14
MAIN
Primary Current Trip error
E462
15
MAIN
Over current trip / PFC over current error
Check OLP sensor
E463
16
MAIN/INVERTER IPM(IGBT Module) Over Current(O.C)
E464
17
MAIN/INVERTER Comp. Over load error
E465
18
MAIN/INVERTER DC-Link voltage under/over error
Check AC Power or DC_Link voltage
E466
19
MAIN/INVERTER Comp. wire missing error
Check Comp. wire
E467
20
MAIN/INVERTER Current sensor error
Check Outdoor Inverter PBA
E468
21
MAIN
Outdoor EEPROM error
Check Outdoor EEPROM date
E471
22
MAIN/INVERTER IPM(IGBT Module) or PFCM Temperature sensor Error Check Outdoor Inverter PBA
E474
23
MAIN/INVERTER PFC Overload Error
Check Outdoor Inverter PBA
E484
24
MAIN/INVERTER IPM is over heated.
Check Outdoor Inverter PBA
E500
25
MAIN
GAS Leak error
Check indoor and outdoor unit model
E554
26
MAIN
Capacity miss match between indoor and outdoor Check indoor and outdoor unit model
E556
Off
Blink
On
The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized
Service Center.
If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB.