OfficeServ 7400 Installation Manual
© SAMSUNG Electronics Co., Ltd.
8-1
CHAPTER 8.
Starting the
System
This chapter describes items to check before starting the OfficeServ 7400 system, the
procedure for starting the system, and the procedure to test the operation of the system.
8.1 Pre-Check
This section describes items to check before starting the OfficeServ 7400 system.
8.1.1 Environment
y
Temperature
Check if the room temperature is between 0
°
C and 45
o
C. If the room temperature is
out of range from the normal operation temperature, install a heating/cooling device to
maintain the normal operation temperature.
y
Humidity
Check if the humidity of the room where the system is installed is between 10% and
90%. Take special caution since humidity affects the electrical components and
connectors of the system.
y
Direct Sunlight and Dust
The room where the OfficeServ 7400 system is installed should be protected from
direct sunlight and should have ventilation systems to prevent the system from
malfunctioning due to dusts.
8.1.2 Safety Conditions
The building where the OfficeServ 7400 system is installed should have lightning rods and
grounding to protect the system against lightning and electric leakage.
y
Check if the OfficeServ 7400 system is not inclined and is maintained horizontally.
y
Do not place devices that may cause electromagnetic interference near the system.
y
Place a fire extinguisher near the system. Since spring coolers can seriously damage
the system, use extinguishers such as Halor 1301 and Carbon Dioxide.
y
Make sure that the input power of the OfficeServ 7400 system is within the range of
AC 100~240 V and other electric devices, such as motors and compressors, do not use
the same input power.
y
Check if the grounding terminal on the rear panel of the system is properly connected
to the external grounding.