Summary of Contents for MIM-E03*N

Page 1: ...EHS MONO Kit EU_IM_05388A 00_EN indd 2 2015 03 18 오전 11 53 30 ...

Page 2: ... installation manual imagine the possibilities Thank you for purchasing this Samsung product EN ES FR IT PT DE DB68 05388A 00 This manual is made with 100 recycled paper EHS MONO Kit EU_IM_05388A 00_EN indd 3 2015 03 18 오전 11 53 30 ...

Page 3: ...Installing the unit 6 Wiring works 9 Wiring schematics 31 Self test mode of wired remote controller 32 Troubleshooting 34 Error codes 37 MixingValve 39 Concrete curing function 42 Installation option setting 43 2 EHS MONO Kit EU_IM_05388A 00_EN indd 2 2015 03 18 오전 11 53 31 ...

Page 4: ...f f The unit contains various electric parts which should be kept out of the reach of children f f Do not attempt to repair move alter or reinstall the unit by unauthorized personnel these operations may cause product damage electric shocks and fires f f Do not place containers with liquids or other objects on the unit f f All the materials used for the manufacture and packaging of the air to wate...

Page 5: ...1EA Flow Switch 1EA 2m Sensor holder 2EA OD 7 8mm Sensor clip 2EA Cable tie 4EA Aluminum tape 2EA Rubber tape 2EA Insulartor 2EA LEAD CONNECTOR Back up heater conector Red Back up heater conector Brown Back up heater conector White Installation manual User manual Temp sensor Temperature sensor MIM E03AN 9 12 14 16 kW outdoor unit MIM E03BN 5 kW outdoor unit 4 EHS MONO Kit EU_IM_05388A 00_EN indd 4...

Page 6: ... kg Packing size W x H x D 329 mm x 439 mm x 168 mm Flow Switch Set Point MIM E03AN 9 12 14 16 kW outdoor unit 16LPM MIM E03BN 5 kW outdoor unit 7LPM Mounting the unit Procedure Remark 1 Remove 2 screw from the unit Screw 2 Open the top cover and install 4 screws on the wall 3 Close the top cover and install 2 screw again into the unit 5 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 5 2015 03 18 오전...

Page 7: ...Installing the unit Installing the remote controller Dimension 120 124 63 8 19 5 Unit mm 6 EHS MONO Kit EU_IM_05388A 00_EN indd 6 2015 03 18 오전 11 53 32 ...

Page 8: ...rt a flat head screwdriver into the square groove in the upper area of the hook to disassemble it easily 2 Arrange the communication cable so that they fit in the housing along the edges of the rear cover If you need more space for the wiring work you can take it off 15 cm When the cable is not concealed When the cable is concealed 10 cm 7 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 7 2015 03 18 ...

Page 9: ...tween the rear and front cover When installing your wired remote controller on the wall consider the size of the wire hole and select a wire with a proper thickness Wire that is connectable to wired remote controller PCB If you install the wired remote controller by reclaiming install it according to ring terminal cable specification If you install the wired remote controller by using four pieces ...

Page 10: ...power connections must be protected from dew condensation by thermal insulation The system shall be earthed Do not earth the unit to a utility pipe surge absorber or telephone earth Incomplete earth may cause electrical problems CAUTION Layout of PCB SMPS circuit Micom LED EEPROM 2 WIRE COMM Load control Fuse No Note FR Control CNS2 Green Flow Switch CNS041 Blue WaterTank CNS042 Yellow Heater Out ...

Page 11: ... OUTPUT AC B5 Neutral OUTPUT AC B6 Lived_INV PUMP OUTPUT AC B7 Neutral OUTPUT AC B8 Lived OUTPUT AC B9 2WAY1_NO OUTPUT AC B10 2WAY1_NC OUTPUT AC B11 Neutral OUTPUT AC B12 Lived OUTPUT AC B13 2WAY2_NO OUTPUT AC B14 2WAY2_NC OUTPUT AC B15 Neutral OUTPUT AC B16 Lived OUTPUT AC B17 3WAY_NO OUTPUT AC B18 3WAY_NC OUTPUT AC B19 Neutral OUTPUT AC B20 Lived OUTPUT AC B21 THERM01_C INPUT AC B22 THERM01_H IN...

Page 12: ...al dimensions for screw mm 4 4 4 8 8 B Standard dimension mm 8 9 5 9 5 12 12 Allowance mm 0 2 0 2 0 2 0 2 D Standard dimension mm 3 4 4 2 5 6 7 1 Allowance mm 0 3 0 2 0 3 0 2 0 3 0 2 0 3 0 2 d1 Standard dimension mm 1 7 2 3 3 4 4 5 Allowance mm 0 2 0 2 0 2 0 2 E Min 4 1 4 1 6 7 9 F Min 6 7 5 9 9 L Max 16 17 5 20 28 5 30 d2 Standard dimension mm 4 3 5 3 4 3 8 4 8 4 Allowance mm 0 2 0 0 2 0 0 2 0 0 ...

Page 13: ... arc If the terminal is connected too firmly the terminal may be damaged f f External force should not be applied to the terminal block and wires f f The cable ties to fasten the wire should be an incombustible material V0 or above The cable ties should be used to fasten the power wire and they are supplied with the unit TighteningTorque kgf cm M3 0 5 0 75 M3 5 8 12 M4 12 18 M5 20 30 f f Main PCB ...

Page 14: ... specialist Check if the grounding resistance is lower than 100 Ω When installing a circuit breaker that can cut the electric circuit in case of a short circuit the allowable grounding resistance can be 30 500 Ω Examples to use cable striper Cable striper 1 Adjust the blade position by coin the controller is at the bottom side of the tool Fix the blade position according to the outer sheath thickn...

Page 15: ...fication Load Power Supply Power Cable Max Length mm2 wires m Do NOT use Heater Water Pump Valve Wired RMC 1Ø 220 240V 50Hz 1 5 3 L 10m 2 5 3 10m L Use Booster Heater Max 3kW 4 0 3 L 10m 6 0 3 10m L f f The power cable is not supplied with Air to water heat pump f f This equipment with IEC 61000 3 12 f f Supply cords of parts of appliances for control kit use shall not be lighter than polychloropr...

Page 16: ...emote controller 2 units Wired Remote Controller Slave Wired Remote Controller Master Connecting a wired remote controller 1 Connect F3 F4 ofTB C kit with F3 F4 of a wired remote controller f f 2 units wired remote controllers are able to be installed onTB C f f When 2 units are installed either one shall has Master setting and another one shall have Slave settings on a wired remote controller 15 ...

Page 17: ...ocation in a DHW 2 Connect the other side of the line at CNS042 Connecting a temp sensor wire to outlet of backup heater 1 Put the sensor side of a temp sensor wire into the designated location in a backup heater 2 Connect the other side of the line at CNS047 Connecting a flow switch 1 Install a flow switch in water line 2 Connect a wire of a flow switch into CNS041 connector Connecting a S G Smar...

Page 18: ...NS042 YEL Use a correct sensor pocket which is fit for the DHW tank sensor OD Ø6 If the gap between the supplied sensor and DHW tank sensor pocket is big use thermal grease 17 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 17 2015 03 18 오전 11 53 40 ...

Page 19: ... the cables to the cable tie mountings with cable ties to ensure strain relief It is of great importance that the heater is filled with water before the electricity is hooked up or else the warranty is not valid If the heater is installed and not used it must be flushed with water once a week CAUTION Connection of the solar circulation pump for DHW tank Description No of wires Max A Thickness Supp...

Page 20: ...t too high and cause the fuse or safety cut off to operate Reduce thermostat setting by 5 C and press the reset button Heating is not working Heating element or internal electrical wiring is out of order Check if there is any power on the power supply on the connector of the heating element between black and yellow green wires If this is OK press the reset button on the fuse safety cut off Water i...

Page 21: ...ly is being shut off Test the free operation of the safety valve regularly by opening the valve ensuring the water flows freely Electrical connection and all servicing of the electrical components should only be carried out by an authorized electrician Fitting and all servicing of plumbing fixtures should only be carried out by an authorized installer When replacing the thermostat safety valve or ...

Page 22: ...necting a booster heater PTC heater allowed limit Max 3kW 1 Directly connect a Booster heater with A3 and A4 inTB A Wire spec 6 0 mm2 regardless of distance Code designation IEC 60245 IEC 57 CENELEC H05RN F NOTE Specification table Part Specification Terminal Block output N L ofTB A1 Connection load Direct connection a booster heater Output N L AC 230V MAX 20A 21 ENGLISH EHS MONO Kit EU_IM_05388A ...

Page 23: ...heater mode is ON at 1st step a control signal of AC 230V goes through CNP003 and CNP001 f f When a backup heater mode is ON at 2nd step a control signal of AC 230V goes through CNP003 and CNP002 1st step 2nd step N L1 N L2 This port can NOT supply enough power for driving a backup heater It s just for providing a ON OFF control signal Maximum current is 0 5A NOTE 22 EHS MONO Kit EU_IM_05388A 00_E...

Page 24: ...ield supply 230V Input L N L N When it set back up boiler on the control kit relay off Boiler Back up boiler L Back up boiler N Boiler When it order to back up boiler operates relay on B4 B5 1 Before the installation control kit should be turned off 2 Using the appropriate equipment to correct position of terminal block as shown on the diagram 3 Make sure EXT CTRL signal of back up boiler must be ...

Page 25: ...mum number of additional pump installation is one inverter pumps Input power 100W 1 Power supply INV Pump Live additional pump Neutral additional pump B6 B1 2 PWM control for INV Pump only Reference GND PWM signal SIG If there is wrong wiring between PWM and reference INV Water Pump may not work or wrong operation CAUTION 24 EHS MONO Kit EU_IM_05388A 00_EN indd 24 2015 03 18 오전 11 53 44 ...

Page 26: ...itional pump B7 B8 Pump Power Terminal of this product is for additional water pump and the maximum allowable current is 0 5 A CAUTION PWM characteristic curve PWM input signal Max Speed The additional pump should be the same type of product as the above graph Recommendation 5 9 kW GRUNDFOS UPM3 25 75 HeatingType 12 16 kW WILO STRATOS PARA 25 1 9 HeatingType 25 ENGLISH EHS MONO Kit EU_IM_05388A 00...

Page 27: ...e Live L 2WAY2 L1 2WAY2 L2 Neutral N 2WAY1 L2 2WAY1 L1 B9 B10 B11 B12 B13 B14 2 way motorized valve f f When outlet water temperature reach to lower than 16 C in cooling mode UFH loops will be closed f f 230V AC f f 2 wires Normal Open or Normal Close 1 Before the installation control kit should be turned off 2 Using the appropriate equipment to correct position of terminal block as shown on the d...

Page 28: ...WTANK 3WAYV V Outdoor Unit FLOOR HEATING A DHWTANK 3WAYV V Outdoor Unit FLOOR HEATING B DHWTANK 3WAYV V Outdoor Unit FLOOR HEATING B DHWTANK 3WAYV V Outdoor Unit Connection of the thermostat escription No of wires Max A Thickness Supply Scope RoomThermostat for weather control 4 22 mA 0 75 mm2 H05RN F or H07RH F Field supply 230V Input N L C1H1 N L C2H2 THERMOSTAT02_HEATING H2 THERMOSTAT01 THERMOS...

Page 29: ...ermostat N L Room thermostat N L Room thermostat N L Before completing installation of Room thermostat check the wiring method in a manual of Room thermostat to output L line WARNING Target zone Zone 1 Thermostat on off controller s output signal Only Heat f f Connect a thermostat on off controller s power to B19 B20 and connect output of a thermostat on off controller to B22 28 EHS MONO Kit EU_IM...

Page 30: ... Terminal 1 RX2 only Electronics Zone 2 on Zone 1 on Zone 1 off Com f f Example of wiring works N L 1 2 3 4 19 20 21 22 23 24 Control kit RF receiver RX1 Cool zone 1 Cool zone 2 Heat zone 1 Com Heat zone 2 29 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 29 2015 03 18 오전 11 53 48 ...

Page 31: ...n of terminal block as shown on the diagram 3 It is for control kit to inform that the pump is operating 4 Solar pump is controlled by installer s handling And it send the signal to control kit depending on solar pump conditions In operating mode signal shall be around 230Vac B W N L In non operating mode signal shall be around 0Vac B W N L Maximun allwable current of each terminal is below 10 mA ...

Page 32: ...Wiring schematics Wiring diagram 31 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 31 2015 03 18 오전 11 53 48 ...

Page 33: ...e corresponding button you can set the load On or Off Enter button Operating part LCD display Red Water pump Booster heater DHW valve Zone 1Valve Back Up Heater 1 Back Up Heater 2 Back Up Boiler Zone 2Valve MixingValve f f When the water pump is turned off the back up heater cannot be turned on f f DHW valve Zone 1Valve Zone 2Valve and MixingValve cannot be turned on at the same time 32 EHS MONO K...

Page 34: ...the previous status will be shown f f For the sensor fault or absence of sensor installation corresponding sensor temperature will be displayed as Er f f When you press the button that does not have a function will blink for 3 seconds f f When pressing the Delete button one time all the loads will be Off f f When all the loads are OFF status Cancel Key input will be ignored and will blink for 3 se...

Page 35: ... is to change parts Display Explanation Wired remote controller thermistor SHORT or OPEN Water Inlet thermistor SHORT or OPEN PHE Outlet thermistor SHORT or OPEN Water outlet Back up Heater temp sensor SHORT or OPEN The Backup heater for using WaterTANK thermistor SHORT or OPEN Outdoor Eva InletTemp Sensor SHORT or OPEN MixingValve thermistor SHORT or OPEN Ref In Ref Out Water Outlet E902 Tr1 Tw2 ...

Page 36: ...ntrol kit Tracking error between remote controller and the Control kit Memory EEPROM Read Write Error Wired remote Controller data error E601 E604 E654 MEMORY EEPROM Read Write Error Wired controller data error EEPROM 35 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 35 2015 03 18 오전 11 53 53 ...

Page 37: ...FF in 15 sec during water pump signal is ON After starting Flow S W ON error In case of flow S W ON in 10min during water pump signal is OFF E911 f f Water pump ON Flow S W off f f Water pump ON Flow S W off NOT enough water flow Water flow 16 7 LPM E912 f f Water pump OFF Flow S W on Water flow 16 7 LPM 36 EHS MONO Kit EU_IM_05388A 00_EN indd 36 2015 03 18 오전 11 53 53 ...

Page 38: ...of OUTDOOR UNIT when it is overload during Safety Start Normal operation state OUTDOOR UNIT 407 Comp down due to high pressure OUTDOOR UNIT 416 Discharge of a compressor is overheated OUTDOOR UNIT 425 Power source line missing error only for 3 phase model OUTDOOR UNIT 440 Heating operation blocked outdoor temperature over 35 C OUTDOOR UNIT 441 Cooling operation blocked outdoor temperature under 9 ...

Page 39: ...7 Communication error between the Master and Salve wired remote controllers Wired Remote Controller 901 Water inlet PHE temperature sensor error open short OUTDOOR UNIT 902 Water outlet PHE temperature sensor error open short OUTDOOR UNIT 903 Water outlet backup heater temperature sensor error CONTROL KIT 904 DHW tank temperature sensor error CONTROL KIT 906 Outdoor evaporator inlet temperature se...

Page 40: ...vs 4 V5011E1213 Actuator LR230A S SSB31 ML6420A3015 Running time 90 sec 150 sec 60 sec FSV 4046 setting 9 15 6 The table above is for your reference It can be changed without advanced notice 4 Set the FSV value by referring to the table below depending on installation environment Function Details Code Unit Default Min Max Mixing valve Use or not 4041 0 No 0 1 Yes Target temperature difference Heat...

Page 41: ...CCW 5 Neutral Description No of wires Max A Thickness Supply Scope Mixing valve 4 22 mA 0 75 mm2 H05RN F or H07RH F Field supply 230V Input Neutral N CCW L2 CW L1 B2 B3 B5 1 Before the installation control kit should be turned off 2 Using the appropriate equipment to correct position of terminal block as shown on the diagram 40 EHS MONO Kit EU_IM_05388A 00_EN indd 40 2015 03 18 오전 11 53 55 ...

Page 42: ...per pipe When the pipe is not a copper pipe Pipe Sensor holder Pipe Sensor Sensor clip Sensor Aluminum tape Sensor Rubber tape Sensor Cable tie insulator insulator When the holder sensor cannot be welded on the pipe fix the senor with aluminum tape and insulate it NOTE 41 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 41 2015 03 18 오전 11 53 55 ...

Page 43: ... operation will continue 2 Temperature of discharge water is controlled as time goes on like below Day Temp 0 10 20 30 40 50 60 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Classification Initial Heating Step raise Heating Step down Total Hour Time 96 48 24 24 24 168 24 24 48 480 Temperature 30 55 30 40 50 55 50 40 30 3 Remaining days are displayed on the wired remote controller during opera...

Page 44: ...ption with remote controller option The procedure of option setting HighTemp Button High Fan Button Mode change LowTemp Button Low Fan Button Entering mode for option setting Option setting mode 43 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 43 2015 03 18 오전 11 53 56 ...

Page 45: ...s Indication Details Indication Details Indication Details 0 D Optionmode 1 6 Tens digit ofSEG 0 9 Unitdigit ofSEG 0 9 Thechanged value 0 F When changing a digit of an control kit address setting option set the SEG3 as A When changing a digit of control kit installation option set the SEG3 as 2 Ex When setting the central controller into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanati...

Page 46: ...MEMO 45 ENGLISH EHS MONO Kit EU_IM_05388A 00_EN indd 45 2015 03 18 오전 11 53 56 ...