Message will appear to alert that tracking is completed. Select the zone initializing
mode and click [OK].
X
No initialization: No zone information initialization will be made.
X
Individual initialization: Initialize zone information as individual mode.
X
Group initialization: Initialize zone information as group mode.
8
Page will be refreshed by clicking [OK]. Then you can check the tracking result.
Note
X
If tracking is executed successfully while ‘NEW’ is set as communication mode for
each channel, virtual OnOff controller will be assigned to each channel.
X
If there is no searched outdoor unit, OnOff controller, SIM/PIM, it is regarded as DVM
tracking failure.
X
If there are devices which have same address, first searched device will be registered
only.
❈
Searching order is not fixed.
X
The number of OnOff controller does not contain the number of virtual
centralized controller.
X
Total number of indoor units includes general indoor units, ERV and AHU .
X
If you execute tracking, system setting will be initialized.
X
If tracking result does not match with actual installation information, there can be
critical error in additional functions such as power distribution.
X
Make sure that tracking information matches to actual installation information
after tracking.