E-
61
Description
Fan Speed and direction
SNVT Type
SNVT_switch: Unsigned/signed Short
Value and operation
Value
State
Auto
0.0
-
Low
1.0
-
Mid
2.0
-
High
3.0
-
Eco
4.0
-
Turbo
5.0
-
Auto
Any>5.0
Stop
-
0
Up-Down
-
1
nvoFanStatus(15), nviFanStatus(4)
Description
ERV Operation Mode
SNVT Type
SNVT_count: Unsigned Long, 2 bytes
Value and operation
( 0: Auto )
1: H/R
( 2: Air purification )
3: Sleep
4: Normal
nvoERVMode(16), nviERVMode(5)
Description
Error Code
SNVT Type
SNVT_count: Unsigned Long, 2 bytes
Value and operation
Valid Range: 0 ~ 999
00 00
→
No Error
Refer to list of Error code
nvoErrorCode(17)
❈
( ) : Function that is not supported now.
❈
Supporting modes are different according to indoor units.
- Indoor unit: Auto, Low, Mid, High
- ERV : Mid, High, Turbo
- AHU Kit: High
* When an indoor unit operation mode is Auto or Dehumid,
Fan speed is controlled as ‘Auto’.
* When an indoor unit operation mode is FAN ONLY, ‘Auto’
cannot be controlled by Fan speed.