background image

+S\-YXNS^SYXO\

installation manual

imagine

 the possibilities

Thank you for purchasing this Samsung product.

To receive more complete service, please 

register your product at

www.samsung.com/register

EN

DB68-03720A(1)

LonWorks

…

 Gateway

MIM-B18N

This manual is made with 100% recycled paper.

uhzh†tptTiX_u†s–•~–™’šGnˆ›Œžˆ †pt†lu†WZ^YWhOXPU•‹‹GGG^Z

YWXZTW[TY\GGG㝘㤸GXWaX]aZ^

Summary of Contents for MIM-B18N

Page 1: ...uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG Y YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 2: ...purchasing this Samsung product To receive more complete service please register your product at www samsung com register EN DB68 03720A 1 LonWorks Gateway MIM B18N This manual is made with 100 recycled paper uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG Z YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 3: ...use inflammable gases near the LonWorks Gateway X Do not install the LonWorks Gateway in a location where it will come into contact with combustible gases machine oil sulphide gas etc X Avoid locations where acid alkali solution or special spray is used X Choose a location that is dry and sunny but not exposed to direct sunlight Suitable temperature is between 0 C 32 F and 39 C 102 2 F X Do not sp...

Page 4: ...TIBLE DEVICES 10 X INSTALLING THE LONWORKS GATEWAY 12 X SETTING THE LONWORKS GATEWAY 20 X READING EHPWATT HOUR METER 25 X SYSTEM SETTING INITIALIZATION 30 X SYSTEM ENVIRONMENT SETTING 31 X TRACKING 44 X DEVICE CONFIGURATION 50 X OVERVIEW FOR FUNCTION 56 X NETWORK PARAMETER CHART 58 X MESSAGE DEFINITION 60 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZ YWXZTW TY GGG㝘㤸GXWaX aX_ ...

Page 5: ...les from centralized controllers interface modules must be installed in such a way that the wires can be connected to the LonWorks Gateway with ease Note X TheLonWorksGatewayisaserverandsupports staticIP ToaccesstheLonWorksGatewaythroughthe internetorwithBMSSystem theLonWorksGateway address whichistheIPaddress mustbeknown X AstaticIPservicefromaninternetserviceprovider mustbeusedifxDSL ADSL VDSL i...

Page 6: ...y or service provider Accessories X The LonWorks Gateway must be installed by a trained installer X Ensure the main power is turned off before installing the LonWorks Gateway X Be sure to use adapter and power cable we provide X The power cable and the communication cable must be installed according to the national electrical wiring regulations uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG YWXZTW TY GGG㝘...

Page 7: ...als during normal operation Ethernet Linked Internet connection indicator Turns green during normal connection Ethernet Active Internet data transmission reception indicator Blinks in orange during normal transmission reception COM1 4 TX Channel 1 4 OnOff controller Outdoor unit Data transmission Indicator Blinks in green during normal transmission COM1 4 RX Channel 1 4 OnOff controller Outdoor unit...

Page 8: ...vice agent checks LonWorks Gateway error status using this terminal SD card socket Sub memory for program update and set information saving socket RS485 Communication Terminal Connect for RS485 communication with devices such as OnOff controller Interface module COM1 COM5 Ethernet Terminal Connect LAN cable Cable tie groove Groove for arranging cables Cable tie groove Reserved SD Card Socket Serial...

Page 9: ... LonWorks Board 10 pin Cable 2 pin Cable Sub Board LonWorks Gateway Interior Main Parts Viewing the Parts Continued Note If you need external circuit configuration consult with the manufacturer Product Dimensions uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG_ YWXZTW TY GGG㝘㤸GXWaX aYX ...

Page 10: ...conventional communicationisapplied setthecommunicationchannelmodeas IM Youcannot connectindoor outdoorunitSETwhichconventionalcommunicationisappliedtonew communicationLonWorksGateway X Whensettingcommunicationchannelmodeas NEW theaddressofvirtualOnOffcontrol willbeassigned Channel0 VirtualOnOffcontroller11 Channel1 VirtualOnOffcontroller12 Channel2 VirtualOnOffcontroller13 Channel4 VirtualOnOffcontrol...

Page 11: ...s Model Note 1 Indoor Unit Outdoor Unit DVM S HR DVM S HP DVM MINI outdoor unit and indoor units which can be connected to DVM S HR DVM S HP DVM MINI outdoor unit 2 OnOff controller MCM A202DN 3 SIM MIM B12 Needed for EHP power distribution 4 PIM MIM B16 Needed for EHP power distribution 5 Watt hour Meter RS485 comm type Connected with SIM Needed for power distribution Please consult Samsung for c...

Page 12: ...ller 75 Must not exceed 15 units per each RS485 communication terminal Outdoor unit 80 Must not exceed 16 units per each RS485 communication terminal SIM PIM 8 Communication mode IM Watt hour Meter 64 Maximum 8 units can be connected to 1 SIM PIM uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGXX YWXZTW TY GGG㝘㤸GXWaX aYY ...

Page 13: ...he installation plate on the rear side of LonWorks Gateway 2 Fix the installation plate on the wall using 4 screws 3 Hang the LonWorks Gateway on the groove which is on the top of the installation plate uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGXY YWXZTW TY GGG㝘㤸GXWaX aYY ...

Page 14: ...onWorks Gateway inside of the wall or wiring from the rear side is needed use wiring groove on the bottom of LonWorks Gateway TopreventbreakdownanddamageofLonWorksGateway and forsafeusage itisrecommendedtoinstallLonWorksGateway onthewall uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGXZ YWXZTW TY GGG㝘㤸GXWaX aYZ ...

Page 15: ...minal X Arrange the adapter as the left figure 3 Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal Then connect Outdoor unit communication cable SOL_COM R1 R2 to the terminal block R1 A R2 B 4 Connect LAN cable to the Ethernet terminal of LonWorks Gateway Then arrange it using cable tie 5 Fasten the bottom cover of LonWorks Gateway and fix it using...

Page 16: ...he adapter as the right figure 3 Separate 1 terminal block from 5 terminal blocks which are attached to RS485 communication terminal Then connect SIM communication cable C1 C2 to the terminal block C1 A C2 B 4 Connect LAN cable to the Ethernet terminal of LonWorks Gateway Then arrange it using cable tie 5 Fasten the bottom cover of LonWorks Gateway and fix it using 2 screws Maximum8SIM PIMunitscan...

Page 17: ...s the left figure 3 Separate Lon terminal block Then connect LonWorks communication cable to the terminal block 4 Connect LAN cable to the Ethernet terminal of LonWorks Gateway Then arrange it using cable tie 5 Fasten the bottom cover of LonWorks Gateway and fix it using 2 screws LonWorkscommunicationcableshouldusethecablewhichfitsto thespecificationprovidedbyEchelon Connecting LonWorks Installing t...

Page 18: ...n Press and hold the SET button for more than 3 seconds You should correctly set up a network according to the installation and communication environment and set the data processing system in advance This Gateway provides data for 128 indoor units However the connectable number of indoor units can be different according to the number of items communication cycle or operating environment Do not conn...

Page 19: ...ApplicMode Display operating mode O X O 13 nvoSetpoint Display desire temperature O X O 14 nvoOnOff Display ON OFF status O O O 15 nvoFanStatus Display wind speed and direction O O X 16 nvoERVMode Display ERV operating mode X O X 17 nvoErrorCode Display Error code O O O 18 nvoDeviceAlarm Remote control Lock Filter Sign Thermo ON OFF Error occurrence status display O O O 19 nvoOccOpMode Cooling onl...

Page 20: ...inquires about the data and the number of indoor units that can be connected is decided by this amount of data For example In the case that HMI inquires about the 27 items of Acknowledged Service Type by an indoor unit When HMI inquires for data at 30 seconds interval 22 indoor units can be connected at 60 seconds interval 44 indoor units can be connected at 120 seconds interval 88 indoor units ca...

Page 21: ...ternet explorer window appears enter IP address http 192 168 0 100 on the address bar then press ENTER 3 If it is the first time to access LonWorks Gateway Install Microsoft Silverlight message will appear X If Microsoft Silverlight have already installed the screen will not appear uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGYW YWXZTW TY GGG㝘㤸GXWaX aY ...

Page 22: ...n After installation access to LonWorks Gateway again Silverlight operates normally with Windows XP SP2 or later version It may not operate normally with previous version of Windows 4 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGYX YWXZTW TY GGG㝘㤸GXWaX aY ...

Page 23: ...ogin with the ID that is included in administration group Factory default LonWorks Gateway ID is admin and password is ac0530 Note X Onlyauthorizeduserscanaccesstowebpage X Connectionspeedmayslowdown Fewerthan5concurrentusersare recommended X LonWorksGatewaymanagershouldchangeIDandpasswordforsecurityand management X Logout Ifyouwanttologout click LOGOUT onthetopofthemenu LonWorks Gatewaywillbeende...

Page 24: ...tch to LonWorks Gateway X If you use accounts with authorization level lower than management group or accounts with general authorization level LonWorks configuration will not be displayed on the menu X If the LonWorks configuration menu does not appear consult the manager 6 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGYZ YWXZTW TY GGG㝘㤸GXWaX aY ...

Page 25: ...ice Configuration screen will appear initially X If you click DMS2 Connect button screen will be switched to initial screen of the DMS2 7 Setting the LonWorks Gateway Continued uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGY YWXZTW TY GGG㝘㤸GXWaX aY_ ...

Page 26: ...ters for name and only available special characters are _ and space X Value for CT proportion should be integer between range of 1 5000 4 Click Save X Changed settings will be saved to the LonWorks Gateway X If you do not click Save changed setting will not be saved 5 Watt hour meter value will display the actual value of electricity on the corresponding watt hour meter Value will be updated autom...

Page 27: ... Set the Monthly baseline setting XYou can select from 1 31 X If you select the last day of the month it will automatically set the last day of corresponding month as baseline Ex Last day of February 28th or 29th 4 Click Save X Changed settings will be saved to the LonWorks Gateway X If you do not click Save changed setting will not be saved 2 4 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGY YWXZTW TY G...

Page 28: ...ly unit X If you select monthly period setting you can select the period in monthly unit 3 Set the period X If you set period in daily unit you can set up to maximum 90 days X If you set period in monthly unit you can set up to maximum 1 month 4 Click Save X Changed setting will be saved to LonWorks Gateway X If you do not click Save changed setting will not be saved Period setting 2 4 3 uhzh tptT...

Page 29: ...dress and the channel information of the SIM PIM interface module which is connected to the watt hour meter X If the SIM PIM interface modules with addresses 0 7 executes tracking it will be displayed as 16 23 in LonWorks Gateway 4 Check the information of indoor outdoor unit which is connected to watt hour meter 3 7 2 1 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGY_ YWXZTW TY GGG㝘㤸GXWaX aY ...

Page 30: ...is 4 6 Set indoor unit to execute power distribution X If you do not set the watt hour meter information the power distribution result of the indoor unit will be displayed as 0 7 Click Save X Changed setting will be saved to LonWorks Gateway X If you do not click Save changed setting will not be saved X Information of watt hour meter connected to indoor outdoor unit should be accurate If the watt ...

Page 31: ... in order from the main menu screen X Caution will be displayed on LCD Display 3 Initialize LonWorks Gateway by clicking Set when caution phrase appears X If you press Menu button system will return to main menu without initialization When initializing system setting all saved data in LonWorks Gateway will be deleted After initialization you must aware that the saved data and IP address will be re...

Page 32: ... 2 Click Edit from the DMS network information section 3 When text boxes of IP Subnet mask Default gateway and DNS server are enabled Enter values for each item X 15 letters can be entered for each item X Each item should match with the network address form 4 Click Save button on the DMS network information section 1 2 4 3 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZX YWXZTW TY GGG㝘㤸GXWaX aY ...

Page 33: ...d access to LonWorks Gateway by entering the IP set and saved manually Note X Factorysettingisasfollows 1 IPaddress 192 168 0 100 2 Subnetmask 255 255 255 0 3 Defaultgateway 192 168 0 1 4 DNSserver 0 0 0 0 X SinceLonWorksGatewaysets192 168 0 254asengineeringIPinternally it shouldbealwaysavailableregardlessofcurrentIP 5 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZY YWXZTW TY GGG㝘㤸GXWaX aY ...

Page 34: ...1 X Hour You can enter from 0 to 23 X Minute You can enter from 0 to 59 X Second You can enter from 0 to 59 4 Click Save button on the System time section 5 When the pop up window appears click OK X When message with Reading data from DMS Please wait appears saving is completed Then System Environment Setting screen appears again with all items disabled Note Systemtimereflectssetcurrentvalue 1 2 3...

Page 35: ... Setting 2 Click Edit from the Select language section 3 Select a language you want and click Save 4 When the pop up window appears click OK LonWorks Gateway will restart and the system will be changed to selected language 1 2 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZ YWXZTW TY GGG㝘㤸GXWaX aZW ...

Page 36: ...ter name of LonWorks Gateway when LonWorks Gateway name field enabled XYou can use maximum 30 letters including English alphabets and special symbols X When LonWorks Gateway name is set the name will be displayed on the top title bar of web browser 4 Click Save after setting is completed 3 1 4 2 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZ YWXZTW TY GGG㝘㤸GXWaX aZX ...

Page 37: ...from LonWorks Gateway Please wait message appears and saving is completed Afterwards system environment setting screen appears again as all items are disabled XYou can check new LonWorks Gateway name on the title bar of web browser Note NameofLonWorksGatewayissettoblankasfactory default 5 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZ YWXZTW TY GGG㝘㤸GXWaX aZX ...

Page 38: ...ue you want when all items fields are enabled X If you select Apply you should enter e mail address SMTP server ID password and SMTP server address X If you select Not apply E mail ID PW and SMTP server items will not affect 4 Click Save after setting is completed 1 4 2 3 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZ YWXZTW TY GGG㝘㤸GXWaX aZX ...

Page 39: ...dow appears 6 Reading data from DMS2 Please wait message appears and saving is completed Afterwards system environment setting screen appears again with all items are disabled Note Infactorysetting Notapply ischeckedanditemfields E mail ID PW SMTPserver areblank uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGGZ_ YWXZTW TY GGG㝘㤸GXWaX aZX ...

Page 40: ... setting is done you may access DMS from upper controllers S NET3 S NET mini Note IftheuppercontrollerusesPublicIP youmustsetthePublicIPofupper controllertoaccessDMSfromthoseuppercontrollers Iftheuppercontroller usesprivateIP youmayaccessDMSfromthoseuppercontrollerswithout settingthePublicIPofuppercontroller PrivateIPrange 10 0 0 0 10 255 255 255 172 16 0 0 172 31 255 255 192 168 0 0 192 168 255 2...

Page 41: ...cy stop Commands to stop all operation of indoor unit except DDC and disable remote control when inputting contact point control signal In level emergency stop status it will not be controllable even if the command is set from upper controller X Pattern 3 Level Operation Stop Level signal input timing It changes operation stop status of all indoor units X Pattern 4 Pulse Operation Stop Disable Ena...

Page 42: ...th all items disabled Note Contactpointcontrolpatternissettopattern1asfactorydefault For extension purpose LonWorks Gateway has total of 10 DI DO ports Contact control and output function is assigned to Ch1 and Ch2 Ch3 Ch10 will be assigned to additional functions For proper contact control connect with Ch1 and Ch2 5 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG X YWXZTW TY GGG㝘㤸GXWaX aZY ...

Page 43: ...ontact signal of port 1 changes from ON to OFF all indoor units will be given Stop command 3 If the contact signal of port 2 is OFF you cannot control all indoor units using remote controller 4 If the contact signal of port 2 changes from OFF to ON you can control all indoor units using remote controller 5 If the contact signal of port 2 changes from ON to OFF you cannot control all indoor units u...

Page 44: ... 3 External contact signal control O Pattern 4 Pulse signal control Emergency Stop Resume Operation No Connection Operation Stop A C Enable Disable remote control Operation Stop A C A C DI Digital Input Circuitry according to Control Switch Pattern uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG Z YWXZTW TY GGG㝘㤸GXWaX aZY ...

Page 45: ...tion that finds system air conditioner devices such as indoor outdoor unit and watt hour meter 4 Setting name for each device You can set name for connected device Set the names to help you recognize the location of the device easily X Communication mode setting for each channel Roles It records what devices are connected to COM1 COM5 of LonWorks Gateway Through tracking LonWorks Gateway searches ...

Page 46: ...ck Edit from the Communication mode by channel screen X Edit button will be switched to Cancel X All selection buttons will be enabled However the channels with searched device maintain its button in disabled status 1 2 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG YWXZTW TY GGG㝘㤸GXWaX aZZ ...

Page 47: ...rt NEW communication mode X When IM is set as communication mode setting will allow tracking monitoring and controlling SIM PIM 4 Click Save after setting is completed X If you click Cancel check boxes will be disabled and Cancel button will switch to Edit 5 When message with Reading data from DMS Please wait appears saving is completed Then System Environment Setting screen appears again with all...

Page 48: ...E 47 DVMTracking 1 Click Device Configuration 2 Click DVM Tracking 1 2 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG YWXZTW TY GGG㝘㤸GXWaX aZZ ...

Page 49: ...mmunication mode setting for each channel Tracking will be executed only to the channels which communication mode is set to either NEW or IM 6 Pop up window with message Tracking is in progress Please wait will appear X Tracking takes from few seconds to 5 minutes However it may vary depending on the number of installed controllers 3 4 5 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG _ YWXZTW TY GGG㝘㤸GXW...

Page 50: ...hchannel X Ifthereisnosearchedoutdoorunit OnOffcontroller SIM PIM itisregardedasDVM trackingfailure X Iftherearedeviceswhichhavesameaddress firstsearcheddevicewillberegistered only Searchingorderisnotfixed X ThenumberofOnOffcontrollerdoesnotcontainthenumberofvirtual centralized controller X Totalnumberofindoorunitsincludesgeneralindoorunits ERV andAHU X If you execute tracking system setting will ...

Page 51: ...e connected devices to LonWorks Gateway will be stopped when you use this function Connect searched device to the other channel and execute tracking If the other device is searched in the channel you want to use use Disconnect all devices function If you use this function LonWorks Gateway device connection status will be initialized 3 4 1 2 Disconnect all devices uhzh tptTiX_u s Gn pt lu WZ YWhOXP...

Page 52: ...a from DMS Please wait appears and all the devices are disconnected page will be refreshed Note X Afterexecuting Disconnectalldevicefunction devicesearchstatusofLonWorks Gatewaywillbeinitialized X Youshouldexecutetrackingagainafterusingdisconnectalldevicesfunction 5 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG X YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 53: ...pplicable device X The Object ID can not be used for more than one piece of device X Object ID can be entered between 1 128 X Device without an Object ID can not transfer its information to LonWorks X Object ID does not appear if there are more than 128 indoor units Checking and changing the Object ID List of equipment connected to LonWorks can be checked when the tracking is completed 3 uhzh tptT...

Page 54: ...dresses from Address colum X Detail information of the selected device will be displayed in device information X User can directly input and change the value of the input type information 1 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG Z YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 55: ...when setting is completed X A When clicking cancel texts become inactive and the cancel will be switched to change 5 When the message with Reading data from DMS Please wait and saving is completed device information page will be displayed again with all the items inactivated Note X ThevalueoftheInputitemrepresentsthecurrentstatusofthedevice Therefore valuemaybedifferentfromthefinalstatuscontrolled...

Page 56: ...urrent status of indoor unit ERV and the value can be different due to synchronization delay with LonWorks MMI and data conversion X Refer to LonWorks Message Definition for device information display for each device uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 57: ...isplay ERV operating mode 17 nvoErrorCode SNVT_count Display Error code 18 nvoDeviceAlarm SNVT_state Remote control Lock Filter Sign Thermo ON OFF Error occurrence status display 19 nvoOccOpMode SNVT_switch Cooling only Heating only setup status display 20 nvoCoolTempLock SNVT_switch Low temperature limit setting status display 21 nvoHeatTempLock SNVT_switch High temperature limit setting status d...

Page 58: ... count 2 DMS system Objects No NV Name NV Type Remarks 1 nciSndHrtBt SNVT_time_sec SCPTmaxSendTime Send Heartbeat 2 nciMinOutTm SNVT_time_sec SCPTminSendTime Minimum Send Time 3 nciMinDeltaTemp SNVT_temp_p SCPTminDeltaTemp Min difference before update 4 nciDelayStatrup SNVT_time_sec SCPTpwrupDelay Delay time after a power up 3 Configuration Properties Unused Network Variables The network variable l...

Page 59: ...tPoint SNVT_temp_p nvoErrorCode SNVT_count nvoUserLockout SNVT_switch nviCoolTempLock SNVT_switch nvoOnOff SNVT_switch nviOnOff SNVT_switch nvoDeviceAlarm SNVT_state nviERVMode SNVT_count nvoEnergyConp SNVT_elec_kwh_l nviHeatlTempLock SNVT_switch nvoRuntimep SNVT_time_hour nvoFanStatus SNVT_switch nviApplicMode SNVT_hvac_mode nvoOccOpMode SNVT_switch nviFilterReset SNVT_switch nvoEnergyCon SNVT_elec...

Page 60: ...In 8 SNVT_switch nvoSystemLock SNVT_switch nvoDMSAlarm SNVT_count nviDigitalOut 6 SNVT_switch nvoSystemAlarm SNVT_count Configuration Properties nciSndHrtBt nciMinOutTm nciMinDeltaTemp nciDelayStatrup nviAllOff SNVT_hvac_emerg uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 61: ...licMode 2 Description Set Temperature SNVT Type SNVT_temp_p Signed Long 2 bytes Value and operation Cool 18 0 C 30 0 C Heat 16 0 C ۙ 30 0 C nvoSetpoint 13 nviSetpoint 3 Description Power ON OFF status SNVT Type SNVT_switch Unsigned signed Short Value and operation Value State OFF 0 0 0 ON 100 0 1 nvoOnOff 14 nviOnOff 1 Invalid Value Automatically set as HVAC_AUTO Invalid Value Automatically set up...

Page 62: ...ERVMode 16 nviERVMode 5 Description Error Code SNVT Type SNVT_count Unsigned Long 2 bytes Value and operation Valid Range 0 999 00 00 No Error Refer to list of Error code nvoErrorCode 17 Function that is not supported now Supporting modes are different according to indoor units Indoor unit Auto Low Mid High ERV Mid High Turbo AHU Kit High When an indoor unit operation mode is Auto or Dehumid Fan s...

Page 63: ...Thermo On Off 1 Thermo On 0 0 No Error nvoErrorCode 1 Error nvoDeviceAlarm 18 Description Operation Mode restriction SNVT Type SNVT_switch Unsigned singed Short Value and operation Value State Unlock 0 0 0 Cool only 1 0 1 Heat only 2 0 1 nvoOccOpMode 19 nviOccOpModeCmd 8 Description Setting monitoring Lower limit temperature and function toggle SNVT Type SNVT_switch Unsigned singed Short Value and...

Page 64: ...umption value after baselin SNVT Type SNVT_elec_kwh_I Signed Quad 4bytes Value and operation Raw range 0 999999 Resolution 0 1 nvoEnergyCon 24 Description Indoor unit usage within the period SNVT Type SNVT_time_hour Signed Long 2bytes Value and operation Raw range 0 65535 nvoRunTimep 25 Description Indoor unit usage after baseline SNVT Type SNVT_time_hour Signed Long 2bytes Value and operation Raw...

Page 65: ...n Remote control restriction SNVT Type SNVT_switch Unsigned singed Short Value and operation Value State Operation remark 0 0 0 Unlock 100 0 1 Level 1 100 0 2 Lock nviUserLockout 7 nvoUserLockout 22 Description Device Information SNVT Type SNVT_str_asc Unsigned Character Array 31bytes Value and operation Refer to Expansion of nvoDevListDesc nvoDevListDesc 27 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG...

Page 66: ...t 14 15 Separator Underbar _ 095 16 Unit type 0 indoor unit 1 AHU 2 ERV 17 Separator Underbar _ 095 18 Operation mode DMS Format 0 Auto 1 Cool 2 Dehumid 3 Fan 4 Heat 19 ON OFF 0 1 20 Fan speed 0 1 2 3 4 5 21 Fan Swing 0 1 22 Error 0 1 23 Separator Underbar _ 095 24 setPoint temperate Second significant digit First significant digit First decimal place 25 26 27 Space temperate Second significant di...

Page 67: ... 0 0 ON 100 0 1 nvoDigitalIn 4 Description System lock status of DMS only monitoring available SNVT Type SNVT_switch Unsigned singed Short Value and operation Value State Unlock 0 0 0 Lock 100 0 1 nvoSystemLock 5 Description DMS Alarm SNVT Type SNVT_count Unsigned Long 2 bytes Value and operation 0 Normal 8 Emergency stop 105 Tracing in progress 108 Tracking failed 109 Lon Module DMS2 communicatio...

Page 68: ...es Value and operation SIM PIM Communication Error Refer to list of Error code nvoSystemAlarm 7 Description All indoor units turn off SNVT Type Enumeration emerg_t Value and operation 0 EMERG_NORMAL 4 EMERG_SHUTDOWN nviAllOff 2 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 69: ...bles the Minimum Send Time mechanism This configuration property defines the maximum period of time that expires before the specified network variable outputs will automatically be updated The associated network variable will also be transmitted as a heartbeat output on a regular basis as dictated by the Maximum Send Time nciSndHrtBt configuration value Valid Range The valid range is any value bet...

Page 70: ...lid range is any value between 0 0 sec and 6 553 4 sec Setting nciDelayStartup 0 0 disables the Start Up Delay mechanism Associate Values All output network variables Recommendations If required set a value greater than 1 minute which is a settle down time of the installed device This configuration property sets the minimum temperature change required before the associated output network variable ...

Page 71: ...E 70 Memo uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG W YWXZTW TY GGG㝘㤸GXWaX aZ ...

Page 72: ...E 71 uhzh tptTiX_u s Gn pt lu WZ YWhOXPU GGG X YWXZTW TY GGG㝘㤸GXWaX aZ ...

Reviews: