E-
89
Description
Setting/monitoring upper limit temperature
and function toggle
SNVT Type
SNVT_switch: Unsigned/signed Short
Value and operation
Operation
Value
State
Unlock
16.0 ~ 30.0
0
Lock
16.0 ~ 30.0
1
Heat: 16.0 °C ~ 30.0 °C
Description
Electric consumption value within the period
SNVT Type
SNVT_elec_kwh_I: Signed Quad, 4bytes
Value and operation
Raw range: 0 ~ 999999
Resolution: 0.1
Description
Electric consumption value after baselin
SNVT Type
SNVT_elec_kwh_I: Signed Quad, 4bytes
Value and operation
Raw range: 0 ~ 999999
Resolution: 0.1
Description
Indoor unit usage within the period
SNVT Type
SNVT_time_hour: Signed Long, 2bytes
Value and operation
Raw range: 0 ~ 65535
Description
Indoor unit usage after baseline
SNVT Type
SNVT_time_hour: Signed Long, 2bytes
Value and operation
Raw range: 0 ~ 65535
❈
Energy consumption and Runtime are the accumulated value
during the user setting period.
❈
The data above is for reference so you can not use them for
official billing.
nvoHeatTempLock(21), nviHeatTempLock(10)
●
nvoEnergyConp(23)
●
nvoEnergyCon(24)
●
nvoRunTimep(25)
●
nvoRunTime(26)
●