E-
14
Cable tie
LAN cable
Connect
communication
cable
Adapter
Connecting Outdoor Unit
1
Unfasten the 2 screws on the bottom of the DMS2.5 front
cover. Hold the bottom 2 sides of the DMS2.5 and push
downwards to slide open the cover.
2
Connect the adapter to the power terminal.
X
Arrange the adapter as the right figure.
3
Separate 1 terminal block from 5 terminal blocks that
are attached to RS485 communication terminal of the
DMS2.5. Then, connect outdoor unit communication
cable (R1, R2)] to the terminal block.(R1
¥
A, R2
¥
B)
4
Connect LAN cable to the Ethernet terminal of DMS2.5.
Then arrange it using cable tie.
5
Fasten the bottom cover of DMS2.5 and fix it using
2 screws.
Maximum 80
Outdoor units
can be connected to one DMS2.5.
Installing the DMS2.5 (Continued)