Troubleshooting for communication error 

When there is a communication error between the digital
electric meter and the power distribution unit, the error
message will be displayed as shown in the picture .

◆ 

Check if the communication cable is connected properly.

◆ 

Check if the PCB switch of the power distribution unit is set

correctly.

◆ 

Check if the communication protocol of the digital electric meter
is set properly.

When there is a communication error between the DVM
air conditioner system and the power distribution unit, 
the error message will be displayed as shown in the
picture.

◆ 

Check if the communication cable is connected properly.

◆ 

Check if any errors are displayed on the outdoor unit.

1

2

Mode

Room

Total 

KWH

KWH

PDU DVM Error

Mode

Room

Total 

KWH

KWH

WHM PDU

Error

 MCM-B102 IM_E_26318  7/25/06 1:43 PM  Page 17

Summary of Contents for MCM-B102

Page 1: ...Power Distribution Unit MCM B102 INSTALLATION MANUAL System Air Conditioner E DB98 26318A 1 ...

Page 2: ...istribution unit WARNING CAUTION Do not use inflammable gases near the power distribution unit Do not install the power distribution unit in a location where it will come into contact with combustible gases machine oil sulphide gas etc Avoid a location where acid alkali solution or special spray is used Install the power distribution unit in a location that is not exposed to direct sunlight and wh...

Page 3: ... ENTERING THE SETUP MODE 8 SELECTING THE SET FAN MODE 9 RETURNING TO THE INITIAL MODE 9 SELECTING THE COMMUNICATION PROTOCOL OF A DIGITAL ELECTRIC METER 10 ENTERING THE INDOOR UNIT FAN POWER CONSUMPTION 12 CHANGING THE PASSWORD 15 TEST OPERATION 16 TROUBLESHOOTING FOR COMMUNICATION ERROR 17 USING THE POWER DISTRIBUTION UNIT 18 INDOOR UNIT FAN POWER CONSUMPTION TABLE 19 SYSTEM SETUP MODE 21 ...

Page 4: ...nsumed electric power of each room For users Displays the total or individual electric power consumption C C C CA A A AU U U UT T T TI I I IO O O ON N N N The power distribution unit must be installed by an installation specialist Ensure the main power is off before installing the power distribution unit All cables must be installed according to the national wiring regulation and make sure the wir...

Page 5: ...E 5 System diagram Communication cable Power supply line Digital electric meter common ELB or NFB Interceptor of air conditioners Main power breaker Power distribution unit MCM B102 DVM air conditioners ...

Page 6: ...wer distribution unit terminal JP201 3 Connect the digital electric meter communication cable to the power distribution unit terminal JP203 4 Reassemble the power distribution unit 5 Installing the power distribution unit The communication cable and the power cable should be installed separately C C C CA A A AU U U UT T T TI I I IO O O ON N N N JP201 JP203 JP202 JP201 JP203 JP202 Indoor Outdoor un...

Page 7: ...tric meter to be installed Adjust the switch as shown in the table below If the DIP switch of the power distribution unit PCB is not adjusted properly communication error may occur C C C CA A A AU U U UT T T TI I I IO O O ON N N N SW1 SW2 SW3 SW4 Switch status Remarks Use RS 485 communication ON ON OFF OFF Factory setting of the switch SW201 ...

Page 8: ...s on the key pad of the power distribution unit in sequence 1 Press the button again when appears on the display 2 Press the button after entering the password when appears on the display The default password is 0000000 3 If there are no key inputs for 3 seconds when appears on the display the display returns to the initial mode C C C CA A A AU U U UT T T TI I I IO O O ON N N N Entering the setup ...

Page 9: ...WH SET Mode Room Total KWH KWH FAN When selecting the SET mode When selecting the FAN mode Press the or button until appears on the display in the setup mode and press the button The mode changes from the setup mode to the initial mode 2 Press the or button until appears on the display in the SET FAN mode and press the button The mode changes from the SET FAN mode to the setup mode 1 1 2 Ent Ent R...

Page 10: ...wice when appears on the display The default communication protocol setting is 1 2 Selecting the communication protocol of the digital electric meter Ent Ent 2 3 Mode Room Total KWH KWH SET Mode Room Total KWH KWH SET Press the button after entering the desired setting of the communication protocol 4 Ent Button Setting 1 2 3 Communication protocol of a digital electric meter Omni RS 485 Korea Micr...

Page 11: ...u press the or button is displayed Press the button is displayed and the setup is saved 7 Press the or button until appears on the display appears on the display 5 Ent Ent Ent 6 1 2 1 2 1 2 Mode Room Total KWH KWH SET Mode Room Total KWH KWH SET Mode Room Total SET Mode Room Total KWH KWH SET ...

Page 12: ...ndicates the indoor unit main address Select the FAN mode and press the button after entering the setup mode 1 Press the button The existing Room number is deleted and you can enter a new setting 2 Entering the indoor unit fan power consumption Ent Ent Ent 2 Press the or button to select the or and press the button You do not have to enter the indoor unit power consumption setting when you select ...

Page 13: ...deleted and you can enter a new setting Press the button until appears on the display and press the button indicates the low fan speed and the existing setting is deleted and you can enter a new setting 6 E 13 2 Ent 2 Press the button after entering the indoor unit power consumption at medium fan mode 9 Press the button after entering the indoor unit power consumption at low fan mode 7 Ent Ent Ent...

Page 14: ...ayed 14 Press the or button until is displayed appears on the display Press the button after entering the indoor power consumption at high fan mode 11 Press the or button until channel is displayed Adjust the indoor unit power consumption setting for other Rooms following step 2 12 Ent Ent Ent Ent 13 1 2 1 2 1 2 1 2 Mode Room Total KWH KWH FAN Mode Room Total KWH KWH FAN Mode Room Total KWH KWH FA...

Page 15: ...ssword 1 2 Press the Ent button is displayed on the display and new password is saved 6 Ent 1 2 Press the button after entering new password You can set the password up to 7 digits Press the button when appears on the display The existing password is deleted and you can enter a new password 2 Ent Ent Ent Ent 3 2 Ent Mode Room Total KWH KWH SET Mode Room Total KWH KWH SET Mode Room Total KWH KWH SE...

Page 16: ...4 Check the communication status by pressing the or button after completing all the settings for the communication protocol Check if the LCD display turns on after powering on the power distribution unit 1 Set the communication protocol between the digital electric meter and the power distribution unit 2 3 Mode Room Total KWH KWH ...

Page 17: ...h of the power distribution unit is set correctly Check if the communication protocol of the digital electric meter is set properly When there is a communication error between the DVM air conditioner system and the power distribution unit the error message will be displayed as shown in the picture Check if the communication cable is connected properly Check if any errors are displayed on the outdo...

Page 18: ...on to select the Room number to check Check the power consumption of each indoor unit 1 Press the to select auto scan or manual scan If the auto scan is selected the consumed power of each room will be scanned automatically and if the manual scan is selected press the or button to select the rooms to check 2 A M ...

Page 19: ...4 AVMCC140EA1 AVXDBH071EA AVMBH020EA4 AVMBC020EA0 AVMBH026EA4 AVMBC026EA0 AVMBH035EA4 AVMBC035EA0 AVMBH052EA4 AVMBC052EA0 AVMBH070EA4 AVMBC070EA0 35 35 40 33 33 33 33 56 56 88 104 140 140 74 74 74 140 140 35 35 40 33 33 33 33 70 70 103 119 150 155 81 81 81 155 155 35 35 40 33 33 33 33 80 80 121 136 165 172 89 89 89 172 172 1 way cassette 2 way cassette 4 way cassette Duct Built in L Low M Medium H...

Page 20: ...020EA1 AVMWH026EA4 AVMWC026EA1 AVMWH035EA4 AVMWC035EA1 AVMWH052EA4 AVMWC052EA1 AVMWH070EA4 AVMWC070EA1 150 150 458 458 458 68 68 68 58 63 35 35 32 32 35 72 85 42 42 42 85 85 170 170 486 486 486 68 68 68 67 72 35 35 32 32 35 72 85 42 42 42 85 85 185 185 513 513 513 68 68 68 75 80 35 35 32 32 35 72 85 42 42 42 85 85 Duct Low static pressure Duct High static pressure Slim Duct Ceiling Wall mounted Pr...

Page 21: ...tiontypesetup Savesetup Restoredefaultfactorysettings Exitfromthesetupmode Representsthemainaddressoftheindoorunit SelectingtheAuto Manualmode IndoorunitFANpowerconsumptionsetup atLmode IndoorunitFANpowerconsumptionsetup atMmode IndoorunitFANpowerconsumptionsetup atHmode Savesetup Exitfromthesetupmode ...

Page 22: ...E 22 MEMO ...

Page 23: ...E 23 ...