8. System configuration
Installer reference guide / Mono tank integrated type
167
8.5 Testing operations and concrete curing function
Testing operations
※
AE080BXYD**, AE120BXYD**, AE140BXYD**
1
Check the power supply between the outdoor unit and the auxiliary circuit breaker.
– 1 phase power supply : L, N
– 3 phases power supply : R,S,T,N
2
Check the control panel
– Check that you have connected the power and communication cables correctly. (If the power cable and
communication cables one mixed up or connected incorrectly, the PCB will be damaged.)
– Check the temp. sensor, drain pump/hose, and display are connected correctly.
3
Press K1 or K2 on the outdoor unit PCB to run the test mode and stop.
K1 (Number of Press)
KEY operation
7-segment display
1 time
Trial operation in Heating mode
“K” “1” “BLANK“ “BLANK“
2 times
Vacuuming (Outdoor unit address 1)
“K” “2” “BLANK “ “1“
3 times
Inverter Fault Detection (Comp #1)
“K” “3” “I “ “1“
4 times
End Key operation
-
K2 (Number of Press)
KEY operation
7-segment display
1 time
Trial operation in Cooling mode
“K” “4” “BLANK“ “BLANK“
2 times
Discharge mode of DC link voltage
“K” ”5” ”o” ”k” (1phase)
“K” ”5” ”n” ”A” (3phase)
3 times
Forced defrost operation
“K” “6” “BLANK“ “BLANK“
4 times
Inverter compressor 1 check
“K” “7” “BLANK“ “BLANK“
5 times
End Key operation
-
K3 (Number of Press)
KEY operation
7-segment display
1 time
Intialize (Reset) setting
Same as initial state
1
3
2
4
ON YKO
1
3
2
4
ON YKO
1
3
2
4
ON YKO
K5 K6 K7 K8
K5 K6 K7 K8
7-segment display
KEY (K1~K4)
4
View Mode : When the K4 switch is pressed, you can see information about our system state as below.
K4 (Number of press)
KEY operation
Display on segment
SEG 1
SEG 2,3,4
1 time
Capacity of outdoor unit
1
16HP g 0,1,6
2 times
Order frequency of the compressor
2
120Hz g 1,2,0
3 times
High pressrue (kg/cm
2
)
3
15.2K g 152
4 times
Low pressrue (kg/cm
2
)
4
4.3K g 043
5 times
Discharge temperature Compressor
5
87˚C g 087
6 times
IPM temperature
6
87˚C g 087
7 times
CT sensor value
7
2A g 020
8 times
Suction temperature
8
-42˚C g -42
9 times
COND OUT temperature
9
-42˚C g -42
10 times
EVA in temperature
A
87˚C g 087
11 times
Compressor top temperature
B
87˚C g 087
12 times
Outdoor temperature
C
-42˚C g -42
13 times
EVI inlet temperature
D
-42˚C g -42
14 times
EVI outlet temperature
E
-42˚C g -42
15 times
Main EEV step
F
2000 g 200
16 times
EVI EEV step
G
300 g 300
17 times
Fan step (ssr or bldc)
H
13Step g 0,1,3
18 times
Current frequency Compressor
I
120Hz g 1,2,0
19 times
EVI SOL EEV step
J
300 g 300
20 times
Inverter pump output
K
100% g 100
K4 (Number of press)
Press and hold the K4
to enter the setting
Displayed content
Display on segment
Page 1
Page 2
1 time
Main version
MAIN
Version (ex. 1412)
2 times
Inverter version
INV
Version (ex. 1412)
3 times
EEP version
EEP
Version (ex. 1412)
4 times
Automatically assigned address of the units
AUTO
SEG1,2
SEG3,4
Indoor unit : “A“, ”0”
MCU : “C“, “1“
Address (ex:07)
5 times
Manually assigned address of the units
MANU
SEG1,2
SEG3,4
Indoor unit : “A“, ”0” Address (ex:15)