Troubleshooting
11-9
11-2-5 Indoor unit EVAP OUT sensor breakaway
Outdoor unit display
Indoor unit display
Judgment method
Causes
(x x x : Indoor unit address occurred error)
(Operation)
(Timer)
(Fan)
(Filter)
(Removing frost)
- Refer to the below judge method
- Indoor unit EVAP IN sensor breakaway
x x x
1. Judge method
1) Cooling operation
2) Heating operation
2. Check method
Check if the indoor unit EVAP OUT sensor is separated, and adjust after assembly.
Tcond, out - Tair, out > 3°C
Tair, in - Teva, in > 4°C
Tair, in - Teva, out > 4°C
Compressor running &
indoor unit on and thermo on
Error contents
OK
OK
NO
OK
Indoor unit EVAP OUT sensor breakaway
High pressure average > 15kg/cm
2
Low pressure average < 5kg/cm
2
Teva, out - Tair, in
≥
3°C
Teva, in - Tair, in
≥
2°C
Tcond, out - Tair, out < 2°C
Compressor running &
indoor unit on and thermo on
Error contents
OK
OK
OK
NO
OK
OK
Indoor unit EVAP OUT sensor breakaway