Phenomenon
Check method
• Operation/Fan error is flickering on the indoor unit.
• t2 error is displayed on the outdoor PCB.
• T-air out is -40˚C.
• Check the resistance of outdoor unit Cond mid sensor.
• Replace the outdoor unit Cond mid sensor and check
S-NET.
11-5-12 Outdoor unit Cond mid sensor open