Samsung Electronics
Troubleshooting
11-40
Phenomenon
Check method
■
After operation over 40 minutes with the
test operation in cooling mode.
■
• T-discharge : 57˚C < 70˚C
■
• 44(T-cond)-33(T-subcool)=11˚C > 10˚C
• Discharge a some refrigerant from the outdoor unit by use of a
charging cylinder.
• After about an hour operation after refrigerant discharging, check the
S-NET. And assure whether it is out of the above conditions.
11-5-2 System refrigerant shortage