11. Installation
Important information: regulation regarding
the refrigerant used
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
CAUTION
•
Inform user if the system contains 5 tCO₂e or more
of fluorinated greenhouse gases. In this case, it
must be checked for leakage at least once every 12
months, according to regulation No. 517/2014. This
activity must be covered by qualified personnel
only. In the case of the situation above, the installer
(or authorized person with responsibility for final
check) must provide a maintenance book, with all
the information recorded, according to REGULATION
(EU) No. 517/2014 OF THE EUROPEAN PARLIAMENT
AND OF THE COUNCIL of 16 April 2014 on fluorinated
greenhouse gases.
1
Please fill in the following with indelible ink on the
refrigerant charge label supplied with this product
and on this manual.
-
the factory refrigerant charge of the product,
-
the additional refrigerant amount charged in
the field and
-
+ the total refrigerant charge. on the
refrigerant charge label supplied with the
product.
Refrigerant type
GWP value
R-32
675
•
GWP: Global Warming Potential
•
Calculating tCO₂e: kg x GWP/1000
Indoor unit
Outdoor unit
Unit
Kg
tCO₂e
①
, a
②
, b
①+②
, c
NOTE
•
Factory refrigerant charge of the product: see unit
name plate
•
Additional refrigerant amount charged in the field
(Refer to the above information for the quantity of
refrigerant replenishment.)
• Total refrigerant charge
•
Refrigerant cylinder and manifold for charging
CAUTION
•
The filled-out label must be adhered in the proximity
of the product charging port (e.g. onto the inside of
the stop valve cover).
•
Make sure that the total refrigerant charge does not
exceed (A), the maximum refrigerant charge, which
is calculated in the following formula: Maximum
refrigerant charge (A)= factory refrigerant charge
(B) + maximum additional refrigerant charge due to
piping extension (C)
•
Here below, the summary table with refrigerant
charge limits for each products.
(Unit:g)
Outdoor Unit Installation
Model
A
B
C
**09******
**12******
1115
965
150