※  In case you want more information about the controllers and accessories, please refer to the Controller and

Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.

11. Installation

Installation of the product

 •

Our units must be installed in compliance with the spaces indicated in the installation manual to ensure either accessibility from 

both sides or ability to perform routine maintenance and repairs. The units’ components must be accessible and that can be 

disassembled in conditions of complete safety either for people or things. For this reason, where it is not observed as indicated into 

the Installation Manual, the cost necessary to reach and repair the unit (in safety, as required by current regulations in force) with 

slings, trucks, scaffolding or any other means of elevation won’t be considered in-warranty and will be charged to end user.

 •

The outdoor unit shall be installed in an open space that is always ventilated.

 •

The local gas regulations shall be observed.

 •

To handle, purge, and dispose the refrigerant, or break into the refrigerant circuit, the worker should have a certificate from an 

industry-accredited authority.

 •

The installation of pipings shall be kept to a minimum.

 •

Do not install the indoor unit in the following areas:

 -

Area filled with minerals, splashed oil, or steam. It will deteriorate plastic parts, causing failure or leakage.

 - Area that is close to heat sources.
 -

Area that produces substances such as sulfuric gas, chlorine gas, acid, and alkali. It may cause corrosion of the pipings and brazed joints.

 -

Area that can cause leakage of combustible gas and suspension of carbon fibers, flammable dust, or volatile flammables.

 -

Area where refrigerant leaks and settles.

 -

Area where animals may urinate on the product. Ammonia may be generated.

 •

Do not use the indoor unit for preservation of food items, plants, equipment, and art works. This may cause deterioration of their quality.

 •

Do not install the indoor unit if it has any drainage problem.

 •

For the multi system, this indoor unit can be conncected to an R-32 or R-410A outdoor unit.  Check the type of refrigerant in the 

outdoor unit.

 •

Because your air conditioner contains R-32 refrigerant, make sure that it is installed, operated, and stored it in a room whose

floor area is larger than the minimum required floor area specified in the following table:

Wall-mounted type

m (kg)

A (m²)

≤ 1.842

No requirement

1.843

4.45

1.9

4.58

2.0 

4.83 

2.2 

5.31 

2.4 

5.79 

2.6 

6.39 

2.8 

7.41 

3.0 

8.51 

 -

m : Total refrigerant charge in the system

 -

A : Minimum required floor area

 •

IMPORTANT: it’s mandatory to consider either the table above or taking into consideration the local law regarding the

minimum living space of the premises.

 •

Minimum installation height of indoor unit is 0.6 m for floor mounted, 1.8 m for wall, 2.2 m for ceiling.

 •

The actual refrigerant charge shall be in accordance with the room size within which the refrigerant containing parts are

installed.

 •

The ventilation machinery and outlets shall be operating adequately and not obstructed.

 •

If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.

 •

Marking to the equipment shall continue to be visible and legible. Markings and signs that are illegible shall be corrected.

 •

Refrigerating pipe or components shall be installed in a position where they are unlikely to be exposed to any substance

which may corrode refrigerant containing components, unless the components are constructed of materials which are

inherently resistant to being corroded or are suitably protected against being so corroded.

11. Installation

Summary of Contents for AR Series

Page 1: ...RAC Technical Data Book RAC forEurope Nordic INV R32 50Hz HP Model AR TX WKNEE Indoor Unit AR TX WKXEE Outdoor Unit...

Page 2: ...History Version Modification Date Remark Ver 1 0 Released AR9500T RAC TDB for Europe Nordic 20 05 29...

Page 3: ...istics C Motion Detect Sensor Wi Fi Tri care Filter E Wi Fi Tri care Filter F Wi Fi H 6 Design Segment A Wind Free GEO C Wind Free AIRISE Y GEO Z AIRISE 7 Version A Z 1 digit 8 Color WK DA White 9 Set...

Page 4: ...Line up IndoorUnit Model Type Design Image AR9500 Wind Free GEO AR5500 GEO AR4500 AIRISE Model Type Design Capacity kW 2 5 3 5 AR9500 Wind Free GEO AR5500 GEO AR4500 AIRISE...

Page 5: ...Model Type Design Capacity kW 2 5 3 5 AR9500 Wind Free GEO AR5500 GEO AR4500 AIRISE Line up OutdoorUnit...

Page 6: ...ity Table 13 3 Dimensional Drawing 19 4 Center of Gravity 22 5 Electrical Wiring Diagram 24 6 Sound Data 26 7 Temperature and airflow distribution 34 8 Piping Diagram 37 9 Operation Limit 38 10 Capaci...

Page 7: ...hile Cross Flow Cross Flow EA 1 1 m min 10 5 10 9 5 8 5 10 9 10 5 9 5 8 5 l s 175 167 158 142 182 175 158 142 m min 11 4 10 9 10 5 9 5 11 9 11 4 10 5 9 5 l s 190 182 175 158 198 190 175 158 BLDC BLDC...

Page 8: ...ct Sensor Wi Fi V Hz 1 2 220 240 50 1 2 220 240 50 F T F T Fin Al Al Tube Cu Cu Anti Corrosion Anti Corrosion BLDC ROTARY BLDC ROTARY KTN130D42UFR KTN130D42UFR kW 4 09 4 09 Type POE POE Initial charge...

Page 9: ...1 1 m min 11 3 9 8 8 2 6 7 11 8 10 3 8 7 7 2 l s 188 163 137 112 197 172 145 120 m min 12 9 11 3 9 8 8 2 12 9 11 3 9 8 8 2 l s 215 188 163 137 215 188 163 137 BLDC BLDC W x n 27 x 1 27 x 1 Drain 16 3...

Page 10: ...Control System Infrared remote control Wired remote control Drain Pump Drain Pump Output Fin Treatment Compressor Model Name Type Output Oil Max lifting Height Displacement Additional Accessories Dra...

Page 11: ...min 11 6 10 1 8 6 6 6 12 1 10 6 9 1 7 1 l s 193 168 143 110 202 177 152 118 m min 13 1 11 6 10 1 8 1 13 1 11 6 10 1 8 1 l s 218 193 168 135 218 193 168 135 BLDC BLDC W x n 27 x 1 27 x 1 Drain 16 3 550...

Page 12: ...ntrol Drain Pump Drain Pump Max lifting Height Displacement Additional Accessories Drain Pump Easy Filter Plus Tri Care Filter Outdoor Unit Power Supply Heat Exchanger Type Material Fan Type Discharge...

Page 13: ...0 2 92 0 83 3 04 2 90 0 86 3 29 2 84 0 90 2 50 2 00 0 56 3 58 2 76 0 93 3 79 2 72 0 93 3 99 2 70 0 93 40 2 74 2 76 0 93 2 86 2 74 0 97 3 11 2 68 1 02 3 29 2 63 1 04 3 39 2 61 1 04 3 59 2 57 1 05 3 78...

Page 14: ...6 2 85 1 19 3 73 3 00 1 23 4 03 3 24 1 29 3 50 2 80 0 92 4 38 3 50 1 34 4 62 3 69 1 35 4 87 3 90 1 34 40 3 39 2 71 1 34 3 55 2 86 1 39 3 84 3 09 1 45 4 06 3 25 1 49 4 18 3 34 1 50 4 42 3 52 1 51 4 66...

Page 15: ...7 2 99 0 81 3 10 2 94 0 85 3 36 2 88 0 89 2 50 2 00 0 54 3 67 2 84 0 91 3 88 2 80 0 92 4 08 2 77 0 91 40 2 81 2 83 0 92 2 93 2 78 0 96 3 18 2 73 1 00 3 37 2 70 1 02 3 47 2 68 1 03 3 67 2 66 1 03 3 87...

Page 16: ...3 2 98 1 17 3 92 3 12 1 23 4 23 3 37 1 28 3 50 2 80 0 89 4 56 3 66 1 31 4 81 3 86 1 32 5 08 4 07 1 32 40 3 52 2 82 1 32 3 71 2 95 1 38 4 00 3 19 1 44 4 22 3 37 1 47 4 33 3 47 1 47 4 57 3 67 1 48 4 83...

Page 17: ...9 2 57 0 61 3 22 2 68 0 71 3 46 2 83 0 83 2 50 2 00 0 54 3 78 2 98 0 89 4 02 3 09 0 90 4 30 3 21 0 88 40 2 93 2 44 0 69 3 05 2 54 0 81 3 28 2 68 0 94 3 47 2 78 0 99 3 58 2 83 1 01 3 82 2 93 1 02 4 09...

Page 18: ...6 3 20 0 86 4 00 3 33 1 01 4 30 3 51 1 18 3 50 2 80 0 89 4 69 3 70 1 27 4 99 3 84 1 28 5 33 3 98 1 25 40 3 65 3 03 0 99 3 79 3 15 1 15 4 07 3 33 1 33 4 32 3 45 1 41 4 45 3 52 1 43 4 75 3 65 1 45 5 08...

Page 19: ...WKNEE Unit mm inches 32 5 16 820 0 1 7 8 48 3 11 3 4 299 2 9 16 65 2 2 1 16 51 9 11 3 4 299 0 2 9 16 65 0 1 1 8 29 0 3 5 16 84 0 2 9 16 65 0 6 15 16 176 0 1 1 8 29 0 16 5 8 422 3 32 5 16 820 0 2 7 16...

Page 20: ...ACWKNEE AR12TXCACWKNEE Unit mm inches 35 889 0 11 3 4 299 0 2 9 16 65 0 9 5 8 245 0 1 1 8 29 0 3 5 16 84 0 1 1 8 29 0 35 889 0 2 1 2 57 9 2 9 16 65 2 11 3 4 299 8 7 16 215 1 7 8 48 3 2 9 16 65 0 16 5...

Page 21: ...WKXEE AR12TXFYBWKXEE AR9500 AR09TXCACWKXEE AR12TXCACWKXEE Unit mm inches 790 601 7 88 7 13 0 135 7 335 9 309 9 2 50 0 4 12 0 548 279 5 509 0 102 1 285 23 6 53 6 31 1 8 23 11 16 13 1 4 12 3 16 1 15 16...

Page 22: ...FZBWKNEE Unit mm inches 35 889 0 215 0 8 1 2 16 406 5 5 9 16 141 3 4 3 16 106 8 299 0 11 3 4 AR5500 AR09TXFYBWKNEE AR12TXFYBWKNEE AR9500 AR09TXCACWKNEE AR12TXCACWKNEE Unit mm inches 41 1 2 1054 5 299...

Page 23: ...4 Centerof Gravity Outdoorunits AR4500 AR09TXFZBWKXEE AR12TXFZBWKXEE AR5500 AR09TXFYBWKXEE AR12TXFYBWKXEE AR9500 AR09TXCACWKXEE AR12TXCACWKXEE Unit mm inches 189 279 155 7 7 16 11 6 1 8...

Page 24: ...P DOWNSTEPMOTOR1 Motor STEP MOTOR WIFI MODULE LOAD WIFI MODULE EVAIN TH Thermistor EVA IN Temp _10Kohm UP DOWNSTEPMOTOR2 Motor STEP MOTOR SUB PBA Printed circuit board SUB BOARD HUMIDITY SENSOR SENSOR...

Page 25: ...OM PCB COND TH Thermistor Cond Out Temp _10Kohm COMP COMPRESSOR BLDC Motor BLDC FAN Motor HEATER Printed circuit board HEATER PCB EEV A Electronic expansionvalve A 4 WAYVALVE 4 WAYVALVE NOTE This wiri...

Page 26: ...2 AR12TXFZBWKNEE 3 AR09TXFYBWKNEE 4 AR12TXFYBWKNEE NOTE Specifications may be subject to change without prior notice Sound pressure Level Sound pressure level is obtained in an anechoic room Sound pre...

Page 27: ...pecifications may be subject to change without prior notice Sound pressure Level Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance...

Page 28: ...EE 3 AR09TXFYBWKXEE 4 AR12TXFYBWKXEE NOTE Specifications may be subject to change without prior notice Sound pressure Level Sound pressure level is obtained in an anechoic room Sound pressure level is...

Page 29: ...ications may be subject to change without prior notice Sound pressure Level Sound pressure level is obtained in an anechoic room Sound pressure level is a relative value depending on the distance and...

Page 30: ...level is an absolute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Model Cooling AR09TXFZBWKNEE 56 AR12TXFZBWKNEE 58 AR09TXFY...

Page 31: ...ject to change without prior notice Sound power level is an absolute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Model Cooli...

Page 32: ...olute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Model Cooling AR09TXFZBWKXEE 59 AR12TXFZBWKXEE 62 AR09TXFYBWKXEE 59 AR12TX...

Page 33: ...ge without prior notice Sound power level is an absolute value that a sound source generates dBA A weighted sound power level Reference power 1pW Measured according to ISO 3741 Model Cooling AR09TXCAC...

Page 34: ...Temperature distribution Discharge angle 30 degree Discharge angle 30 degree AR12TXFZBWKNEE Cooling airvelocity distribution Cooling Temperature distribution Discharge angle 20 degree Discharge angle...

Page 35: ...ating airvelocity distribution Heating Temperature distribution Discharge angle 30 degree Discharge angle 30 degree AR12TXFYBWKNEE Cooling airvelocity distribution Cooling Temperature distribution Dis...

Page 36: ...ating airvelocity distribution Heating Temperature distribution Discharge angle 30 degree Discharge angle 30 degree AR12TXCACWKNEE Cooling airvelocity distribution Cooling Temperature distribution Dis...

Page 37: ...sor Top T_CT Heat Exchanger Main Outdoor unit HX_M SolenoidValve 4Way V_4W Thermistor CondOut T_CO OutdoorFanMotor OFM INDOOR UNIT OUTDOOR UNIT Thermistor Ambient T_A Electronic ExpansionValve Main E_...

Page 38: ...Limit Cooling Heating IndoorTemperature DB Outdoor Temperature DB 20 10 0 10 20 30 40 50 60 70 10 15 20 25 30 35 40 Operation Range 46 16 32 IndoorTemperature DB Outdoor Temperature DB OperationRange...

Page 39: ...5 10 12 5 15 Level Difference m 8 0 96 0 94 0 91 5 0 99 0 97 0 95 0 92 0 1 0 98 0 96 0 93 5 0 99 0 97 0 95 0 92 8 0 96 0 94 0 91 Heating Pipe Length m 5 10 12 5 15 Level Difference m 8 0 96 0 94 0 91...

Page 40: ...d settles Areawhere animals mayurinate on the product Ammonia maybe generated Do not usethe indoorunitforpreservation offood items plants equipment and artworks This maycause deterioration oftheirqual...

Page 41: ...s may look different from the images depicted here Evaporator fancoil indoor Maximum pipe height Maximum pipe length Refrigerant lines electric and drain Compressor condenser outdoor Unit m Model Pipe...

Page 42: ...the manufacturer could void the manufacturer s warranty To determine where to locate the indoor and outdoor units you must survey the entire site and consider many variables The goal is to select loca...

Page 43: ...ng the weight of both the L bracket and the outdoor unit If the unit falls it may result in crushing electric shock fire or explosion that could cause death severe personal injury or property damage I...

Page 44: ...can block the sea breeze and the height and width of the wall should be 1 5 times larger than the size of the outdoor unit You must secure more than 700 mm of space between the protection wall and the...

Page 45: ...ructions 4 Using six field supplied mounting screws and anchors if applicable attach the bracket to the wall Screw Location x 4ea Level Drilling the wall penetration 1 Determine the position of the ho...

Page 46: ...ncables WARNING Do not modify the power cable in any way Doing so may cause electric shock or fire due to poor connection poor insulation or current limit override Make sure to comply with the technic...

Page 47: ...es the R 32 refrigerant be cautious not to generate a spark bykeeping the following requirements Do not remove the fuseswith poweron Do not disconnect the powerplug from thewall outlet with poweron It...

Page 48: ...ground for installation Ensure that the drained water runs off correctly and safely Allow enough separation distance between the product and the ground 80 mm Estimated snow fall Snow proof hood Groun...

Page 49: ...s Adding refrigerant if needed The outdoor unit is charged with sufficient R 32 refrigerant to support up to a 5 m line set For lengths greater than 5 m you must add 15 g of refrigerant per meter of a...

Page 50: ...bel supplied with this product and on this manual the factory refrigerant charge of the product the additional refrigerant amount charged in the field and the total refrigerant charge on the refrigera...

Page 51: ...ead Office Suwon Korea 129 Samsung Ro Yeongtong Gu Suwon City Gyeonggi Do Korea 16677 Website www samsung com https partnerhub samsung com Email airconditioner samsung com Images and data in this book...

Reviews: