Troubleshooting
5-3
Samsung Electronics
5-2-2 When the Indoor Unit Fan Does Not Operate. (Initial Diagnosis)
1) Checklist :
(1) Is the indoor unit fan motor properly connected with the connector (CN72)?
(2) Is the AC voltage correct?
(3) Is HALL IC in indoor fan motor properly connected with the connector (CN42)?
(4) Is the running capacitor (CR71) properly connected with PCB board?
2) Troubleshooting procedure
After unplugging out the power cord should
be reconnected within five seconds.
Does the STD lamp blink?
Does the Solid State Relay(SS71) work
properly?
Is the supply voltage of the fan
motor sufficient?
Test rod location
PCB CN72
Condition
Fan operate
about AC 180V
Normal
voltage
pin #3 and #5
YES
YES
YES
NO
NO
NO
Check as in the procedure “NO power parts”
Refer to page 5-2.
Microcomputer is out of order.
PCB is
out of order.
PCB should be
replaced.
Replace MFC
Fan motor
should be replaced.
Fan motor
is out of order.
MF-C is out of order
YES
-
Test rod location
+
SS71-
SS71-
12V
Normal
Voltage
DB98-04444A(1)-1 4/9/02 2:19 PM Page 5-3
Summary of Contents for AQA07C5(6)ME
Page 3: ...Samsung Electronics 1 2 MEMO...
Page 38: ...MEMO 5 13 Samsung Electronics...
Page 47: ...MEMO Samsung Electronics 6 9...
Page 49: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 ASS Y MAIN PCB TOP PATTERN...
Page 51: ...Samsung Electronics 8 3 8 2 ASS Y MAIN PCB DB93 00437A BOTTOM PATTERN...
Page 53: ...MEMO Samsung Electronics 8 5...
Page 54: ...9 1 Samsung Electronics 9 Wiring Diagrams 9 1 Indoor Unit...
Page 56: ...MEMO 9 3 Samsung Electronics...
Page 57: ...Samsung Electronics Samsung Electronics 10 2 10 1 10 Schematic Diagrams 10 1 Indoor Unit...
Page 58: ...MEMO Samsung Electronics 10 3...
Page 60: ...ELECTRONICS Samsung Electronics Co Ltd Apr 2002 Printed in Korea Code No DB98 04444A 1...