Troubleshooting
5-5
Samsung Electronics
5-2-4 When the UP/DOWN Louver Moter Does Not Operate. (Initial Diagnosis)
1)
Checklist :
(1) Is input voltage normal?
(2) Is the UP/DOWN louver motor properly connected with the connector (CN61)?
2 )
Troubleshooting pro c e d u re
Remove power cord and plug in again in approx. 5 seconds.
Is operating lamp blinking?
Does operation start when swing button of the remote con-
trol unit pushed?
Voltage at pin #33-#36 of micom (ICO4)
change?(Squarewave)
Volatge at pin #10, #11, #12, #13 of IC05 (KID65003)
change?(Squarewave)
UP/DOWN louver motor is faulty.
Driver IC05 (KID65003) is faulty.
Micom (IC04) is faulty.
Normal
Check as in the procedure "No Power
parts". Refer to page 5-2.
Y
Y
N
N
N
Y
Y
Y
5-2-5 In the mode, When there is no warm air current. Check this first;
(1) Is the set temperature of Remote Control lower than room temperature in Heat mode?
(2) Is the Indoor PCB properly connected with the CN71 connector?
After training on, the heating operation should
start in five minutes.
Is the munber #60 of Micom (IC04) DC 4.8 V?
Is the munber #15 of IC07 (KID65003) LOW?
Is the voltage between CN71 #3 and RY71 NO
3
AC198~264?
Abnormal 4way valve of Outdoor Unit.
or connecting Cable
4 way valve should be replaced
or connecting Cable Check.
NO
YES
YES
YES
NO
NO
NO
YES
Normal
Abnormal Micom
Abnormal IC07
Abnormal RY73
PCB should be replaced.
Summary of Contents for AM18A1(B1)E09
Page 2: ...Samsung Electronics Co Ltd DEC 1998 Printed in Korea Code No DB81 10176A 2...
Page 4: ...1 2 Samsung Electronics MEMO...
Page 8: ...2 4 Samsung Electronics MEMO...
Page 24: ...3 16 Samsung Electronics MEMO...
Page 38: ...Samsung Electronics 6 1 6 Exploded Views and Parts List 6 1 Indoor Unit...
Page 40: ...Samsung Electronics 6 3 6 2 Outdoor Unit 11 10 2 10 3 10 5 10 4 10 1 10...
Page 44: ...6 7 Samsung Electronics MEMO...
Page 46: ...Samsung Electronics 8 1 8 PCB Diagrams 8 1 Main PCB...