Satisfying cooling & heating comfort
The Maximum Capacity of outdoor unit at design condition calculated from Samsung capacity data table or design
tool (DVM Pro) should always be the same or greater than System Peak Load (Block Load) defined in table 1.
Time
Room A
Room B
Room C
Room D
Room E
Room F
Total
Music Room Class room
Class room
Class room
Class room
Class room
09:00
8.4
8.0
8.4
8.0
8.4
8.6
49.8
12:00
9.2
8.8
10.8
8.6
10.8
9.8
58.0
14:00
10.0
9.6
9.6
9.6
11.4
10.8
61.0
16:00
11.0
10.6
8.8
10.8
9.6
9.6
60.4
18:00
9.4
9.0
8.8
9.0
9.0
8.4
53.6
Table 1. Example of System Peak loads
f
Zone Peak Loads ( ): To satisfy the demand for each room any time
-
Sum of Zone peak Loads = 65.4kW (11.0 + 10.6 + 10.8 + 10.8 + 11.4 + 10.8)
f
Block load ( ): Total peak load at a given time of day
.
-
Sum of Zone Peak Loads at 14:00 = 61.0kW
• When a system combination ratio is over 130%, a max system capacity is the same as the published
capacity in TDB capacity table at the combination ratio of 130%
NOTE
Cooling Operation Only
When only cooling operation is used, CR is allowed up to 180% if the Max Capacity of outdoor unit is greater than
System Peak Load (Block load) as shown table 2.
Outdoor unit
All capacities of H/P & H/R model
Indoor unit
All indoor unit types
Operation Condition
Cooling mode only
Allowable CR
180%
Table 2. Allowable CR in only cooling operation
• Table 2 shows a standard for allowable CR of cooling only model. Samsung Electronics is not
responsible for any problem caused by using a heating mode at the site with a system designed by
table 2. If heating operation is required, extended CR design must follow section “Allowable CR limit to
avoid abnormal sound level risks in heating operation.”
NOTE
Combination Ratio (Connection Ratio)
Design Procedure & Combination Ratio