Choosing the installation location
10. Installation
Module installation
•
For <Case 1> or <Case 3>
– Height of the wall on the front side should not be higher than
1500mm (60inch).
– Height of the wall on the air inlet side should not be higher than
500mm (20inch).
– Height of the wall on the side is not limited.
– If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the
exceeded height] should be added to the service space (S1, S2).
Unit : mm (inch)
<Case 3>
Ov
er
5
00
(2
0)
Ov
er
5
00
(2
0)
Ov
er
6
00
(2
4)
Over 100 (4) Over 100 (4)
Over 100
(4)
Over 100 (4)
Over 100 (4)
Over 100 (4)Over 100 (4)
Over 100
(4)
Front side
Front side
<Case 2>
Ov
er
20
0
(8
)
Over 300 (12)
Over 400
(16)
Over 400
(16)
Height of
the wall is
unlimited
Front
side
<Case 1>
Ov
er
10
0 (
4)
Ov
er
3
00
(12
) (
S2
)
Ov
er
5
00
(2
0)
(S
1)
Over 100 (4)
Over
100 (4)
Over 100(4)
Front
side
15
00
(6
0)
h1
50
0
(2
0)
h2
Fr
on
t s
id
e
Ai
r i
nl
et
si
de
S1+h1/2
S2+h2/2
Unit : mm (inch)