DVM S
2
HP (460V)
• Make sure
to
use an indoor
unit
that
is
compatible
with
DVM
S2.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• The standard allowed combination ratio of the total rated indoor unit capacity o
v
er the rated outdoor unit capacity
is 50~130%.
C
ombination ratio of up to 1
8
4% is allowed depending on operation mode, minimum operation ratio and
connected indoor unit models. DVM
P
ro 2 design software supports designing o
v
er 130% based on system
design.
R
efer to the
“
Design
P
rocedure
&
C
ombination
R
atio
”
section of this document for details
※ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be
assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
※ Maximum 32 Wall-mount type indoor units with EEV (AM∗∗∗∗NQD∗∗∗, AM∗∗∗NVD∗∗∗) can be connected.
NOTE
SystemModel
Capacity(Ton)
Capa
(Ton)
Model Name
Number of
individual
outdoor
units
6
8
10
12
14
16
18
20
6
AM072BXVGJH/AA
1
1
8
AM096BXVGJH/AA
1
1
10
AM120BXVGJH/AA
1
1
12
AM144BXVGJH/AA
1
1
14
AM168BXVGJH/AA
1
1
16
AM192BXVGJH/AA
1
1
18
AM216BXVGJH/AA
1
1
20
AM240BXVGJH/AA
1
1
22
AM264BXVGJH/AA
2
1
1
24
AM288BXVGJH/AA
2
1
1
26
AM312BXVGJH/AA
2
1
1
28
AM336BXVGJH/AA
2
1
1
30
AM360BXVGJH/AA
2
1
1
32
AM384BXVGJH/AA
2
2
34
AM408BXVGJH/AA
2
1
1
36
AM432BXVGJH/AA
2
2
38
AM456BXVGJH/AA
3
1
1
1
40
AM480BXVGJH/AA
3
1
1
1
1. Combination Table : Outdoor units