22
Refrigerant pipe installation
English
Instal
lation Pr
oc
edur
e
• Amount of additional refrigerant for each indoor unit ( )
(Unit: kg)
Model
Refrigerant Amount (kg /Unit)
1.5
1.7 2.2 2.8 3.2 3.6 4.0 4.5 5.6 6.0
7.1
8.2
9.0 9.3
11.0 11.2 12.8 14.0 16.0 18.0 22.0 22.4 25.0 28.0 32.0 50.0 500CMH 1000CMH
Interior 1way cassette (JSF-0)
(AM***HN1DEH/**)
(AM***NN1PEH/**)
0.15 0.15
Slim 1way cassette (JSF-1/JSF-2)
(AM***F(J/N)N1DEH/**)
0.25 0.25
0.25
0.32
0.32
2way cassette
(AM****N2DEH/**)
0.31
0.47
4way cassette S(600x600)
(AM****NNDEH/**)
0.29
0.29 0.29
0.29
0.37 0.37 0.37
4way cassette S
(AM***F(N)N4DEH/**)
0.45 0.45
0.45
0.45
0.57
0.69 0.69
4way cassette S
(AM****N4FEH/**)
0.69
0.69 0.69
1.00 1.00 1.00 1.00 1.00
1.00
360 cassette
(AM***KN4DEH/**)
0.45 0.45
0.45
0.45
0.69 0.69 0.69
Duct S (AM****NMPKH/**)
0.22
0.22 0.22
0.22
0.31
0.38 0.38 0.38
Duct S (AM****NMPKH9**)
0.31 0.31
0.38 0.38
0.38
Duct S (AM***HNHPKH/**)
0.38 0.38 0.38
Home Duct (AM***KNLDEH/**)
0.13 0.13 0.13
0.17
Home Duct (AM***MNLDEH/**)
0.24 0.24
0.31
Slim duct (AM***FNLDEH/**)
0.17 0.17 0.17
0.26
0.35 0.35
0.45
0.42
0.42 0.62 0.62
Slim duct(with drain pump)
(AM***KNLDEH/**)
0.35 0.35
0.45
0.42
0.42 0.62 0.62
Slim duct (AM***FNLF(P)EH/**)
0.62
0.45 0.45
0.62
0.62
0.62
Slim duct (AM***NNLFEH/**)
0.62 0.62
MSP duct (AM****NMDEH***)
0.24 0.24
0.24
0.28 0.28
0.28
0.32
0.54 0.68 0.68
0.91
HSP duct (AM****NHDEH/**)
0.68 0.68 0.68
1.18
1.18
HSP duct (AM****NHF(P)EH/**)
1.18
1.18 1.18 1.18 1.18 1.18
1.18
Big duct (AM***JNHF(P)KH/**)
1.15
1.15
OAP duct (AM****NEPEH/**)
0.68
1.18
1.18
Concealed Floor Standing
(AM****NFDEH/**)
0.22
0.32
0.32
Floor Standing
(AM****NPDKH/**)
0.69
1.85
Ceiling (AM****NCDEH/**)
(AM****NCDKH/**)
0.39
0.39
0.56
0.95
Console (AM****NJDEH/**)
0.16 0.27
0.27
0.27 0.27
Wall mounted (Neo forte)
(AM***F(H)NTDEH/**)
0.24
0.24 0.24
0.24
0.36
0.36
Wall mounted(Neo forte with EEV)
(AM***F(H)NQDEH/**)
0.34
0.34 0.34
0.34
0.51 0.51
0.51
Wall mounted(AR5000)
(AM****NADKH/**)
0.16
0.16
0.19
0.25
0.25 0.52
0.52 0.52
Wall mounted(AR5000 with EEV)
(AM****NVDE(K)H/**)
0.22
0.22 0.25
0.34
0.34 0.71
0.71 0.71
Wall mounted(Boracay)
(AM***KNTDEH/**)
0.24
0.24 0.32
0.32
0.49 0.49
0.49
Wall mounted(Boracay with EEV)
(AM***KNQDEH/**)
0.24
0.24 0.32
0.32
0.49 0.49
0.49
Wall mounted(MAX4 with EEV)
(AM***MNQDEH/**)
0.68
ERV plus (AM****NKDEH/**)
0.11
0.36
Hydro Unit HE (AM****NBDEH/**)
0.60
0.70 1.20
Hydro Unit HT (AM****NBF*B/**)
0.60 note
1)
MCU (MCU-S*NE**N)
0.50
4Way CST (AM***AN4PKH/**)
0.45
0.45
0.45 0.60
0.60
0.73
0.73 0.88 0.88
LSP Duct (AM***ANLDKH/**)
0.13 0.13 0.13
0.17
0.24 0.24
0.31
MSP Duct (Duct S)
(AM***ANMPKH/**)
0.45 0.45
0.45
0.45 0.45
0.45
0.80
0.84 0.84 0.84
HSP Duct (Duct S)
(AM***ANHPKH/**)
0.80
0.80
0.84
0.84 0.84 0.84
A3050 (AM***JNADKH/**)
0.16
0.16
0.19
0.25
0.25 0.52
0.52 0.52
A3050(with EEV)
(AM***JNVDKH/**)
0.22
0.22 0.25
0.34
0.34 0.71
0.71 0.71
QMD RAC (AM***TNADKH/**)
(AM***TNVDKH/**)
(AE***TNXDEG/**)
0.23
0.23 0.32
0.32
0.48 0.48
0.48 0.64
※
If there is no additional refrigerant value for the indoor unit in the above table, refer to the indoor unit installation manual.